Rev 2.0 : X11CA-IM MASTER MODULE

5

4 MODBUS COMMUNICATION PROTOCOL

4.1 Slave Address Setting

The Slave Address switch (SW1 or SW3, depending on the revision of the PCB) on
the X11CA-IM Module sets the Slave Address of the X11CA-IM Master Module
for MODBUS RTU communication as shown below.

Slave

address

SW1-1

SW1-2

SW1-3

SW1-4

1

OFF

OFF

OFF

OFF

2

ON

OFF

OFF

OFF

3

OFF

ON

OFF

OFF

4

ON

ON

OFF

OFF

5

OFF

OFF

ON

OFF

6

ON

OFF

ON

OFF

7

OFF

ON

ON

OFF

8

ON

ON

ON

OFF

9

OFF

OFF

OFF

ON

10

ON

OFF

OFF

ON

11

OFF

ON

OFF

ON

12

ON

ON

OFF

ON

13

OFF

OFF

ON

ON

14

ON

OFF

ON

ON

15

OFF

ON

ON

ON

16

ON

ON

ON

ON

Table 4-1 Setting Modbus Slave Address

4.2 Data Communication Format

The data format for Modbus communication is 19200, no parity, 8 bit and 1 stop
bit.

4.3 Modbus RTU Protocol Function 3: Read the Holding Registers

To read the binary contents of the holding registers on the X11CA-IM from a host
device, use Modbus RTU Protocol function 3.

Query

The query message specifies the starting register and the quantity of registers
to be read. Registers are addressed starting at zero: registers 1-16 are addressed
as 0-15.