1 setting the user pin number, 292, enable theft monitor, 1 setting the user pin – Ronan X76CTM User Manual

Page 20

Advertising
background image

19

Report 8 (Cont.)

Report 9:

Contacts Settings.

Report 10:

Relays Settings.

Horn:

No

Scripts:

Normal: none

Alarm: none

X110: 7

on QuickTest

Relay: none

Horn:

Yes

Scripts:

Normal: none

Alarm: none

X110: 8

on PreciseTest

Relay: none

Horn:

Yes

Scripts:

Normal: none

Alarm: none

X110: 8

on HiLeak

Relay: none

Horn:

Yes

Scripts:

Normal: none

Alarm: none

X110: 8

on Csld

Relay: none

Horn:

Yes

Scripts:

Normal: none

Alarm: none

X110: 8

Ronan Engineering LDM

21200 Oxnard Street

Woodland Hills CA 91367

** Contacts settings **

** 08/06/99 10:29:20 **

1 SupPipeSump

State: Normal

Logic: Norm.Open

Relay: SuperPSD

2 SupFullSump

State: Normal

Logic: Norm.Open

Relay: SuperPSD

3 SupAnnular

State: Normal

Logic: Norm.Open

Relay: SuperPSD

4 RegPipeSump

State: Normal

Logic: Norm.Open

Relay: UnleadedPSD

5 RegFullSump

State: Normal

Logic: Norm.Open

Relay: UnleadedPSD

6 RegAnnular

State: Normal

Logic: Norm.Open

Relay: UnleadedPSD

7 RegPipeSump

State: Normal

Logic: Norm.Open

Relay: RegularPSD

8 RegFullSump

State: Normal

Logic: Norm.Open

Relay: RegularPSD

9 Probe input

10 Probe input

11 Probe input

12 RegAnnular

State: Normal

Logic: Norm.Open

Relay: RegularPSD

13 Disp#1

State: Normal

Logic: Norm.Open

Relay: none

14 Disp#2

State: Normal

Logic: Norm.Open

Relay: none

15 Disp#3

State: Normal

Logic: Norm.Open

Relay: none

16 Spare

State: Normal

Logic: Norm.Open

Relay: none

Ronan Engineering LDM

21200 Oxnard Street

Woodland Hills CA 91367

*** Relays settings ***

** 08/06/99 10:29:27 **

1 SuperPSD

State: Open

Logic: Norm.Open

Timeout: 0 s

2 UnleadedPSD

State: Open

Logic: Norm.Open

Timeout: 0 s

3 RegularPSD

State: Open

Logic: Norm.Open

Timeout: 0 s

4 RemoteCTA

State: Closed

Logic: Norm.Closed

Timeout: 30 s

normally closed), current
state (alarm/normal), and
the relay to be activated
depending on the contact
state. This report prints the
settings for all contacts,
including the level gauge
probe inputs.

10.

Relays Settings.

Prints

the current settings for the
76CTM relays. For each re-
lay (total of 4 relays) the
current state, logic (normal-
ly open/normally closed)
and the time-out is report-
ed. If the time-out is 0, the
relay will stay in this state
until changed.The time-out
option is for unattended
stations, to increase the
external horn life, if
attached or in applications

where a plulse is required
for remote alarm indication
of multiple alarms (reflash).

.

.

292, Enable Theft
Monitor

The theft alarm is defined as
the activity of the tank (sale or
withdrawal) when the tank is
declared as inactive. To start
theft monitoring, use Function
292. The current net volume is
recorded and the system moni-
tors the net volume for changes.
If the net volume decreases
more than the threshold value
(default 10 gal), a theft alarm is
generated. The net volume
change will be recorded. For
every occurrence, the amount is
recorded, until the function is
disabled. The theft monitoring
can be disabled using Function
291.

10.1 Setting the User Pin

For security purposes,
the X76CTM is designed
so that only the adminis-

Advertising