Edit the relay name, and press [ENT.]. (By default,
the relays are named RELAY1-4).

Enter relay name
Relay 1

Enter the relay time-out (0-255 s), and press
[ENT.]. Entering 0 means that there is no time-out.

Enter relay time-out
25 s

Select the relay logic (1 for normally open, 2 for
normally closed) using [C/CE].

Select relay logic
1-NormOpen

2-NormClose

.

.

44, Set Up Contact [HI, LO]

The X76CTM can have up to 16 contacts, depend-
ing on the number of active probes. Each contact is
enabled and set up individually. If some or all probe
terminals are not used with a probe, they can be
used as a contact input.

Scroll through the contacts using [HI] and [LO].
When the desired contact number and name is dis-
played, press [ENT.].

Set up contact (HI,LO)-1
INPUT 01

The X76CTM asks whether you want to enable the
contact. If the contact is not enabled, the function

ends without changes. If the contact is enabled, the
display prompts for the contact name. Enter or con-
firm the contact name.

Enable contact YES
Use C/CE to toggle

The next prompt allows you to select the contact’s
logic, either N.O. (normally open) or N.C. (normally
closed). Select the desired polarity using [C/CE].

Contact logic (use C/CE)
Norm. Open

Select the relay that will be energized when the
contact is in active (alarm) state. Select 0 for
NONE.

Select alarm relay (HI, LO) 0
NONE

After selecting the alarm relay, press [ENT.].

For the horn to sound while the contact is in alarm
state, the option must be entered using [C/CE].

Horn on alarm
use C/CE to toggle

The system will prompt to set up contacts names.
By default, all contacts have the name INPUT01 -
INPUT16.

Leak Detected.

This event is made active when a

test with a maximal duration was ended, the proba-
bility of leak detection is higher than 95%, and the
leak detected was higher than the threshold (typi-
cally 0.2 gph).

High Leak Detected.

This event is activated when

a maximal duration leak test is completed and the
leak detected is higher than the High Leak
threshold.

Low Volume Alarm.

The volume of the product in

the tank is below the threshold.

Low-Low Volume.

High Volume Alarm.

The volume of the product in

the tank is above the threshold.

High-High Volume.

High Water.

The water level is above the threshold.

Probe Alarm.

A probe failed or was restored.

To setup an event, select Function 82. Select the
type of the event to be programmed. Select the
relay to be assigned, or press [C/CE] to remove an
assignment. Select the horn activation flag by tog-
gling the current selection using [C/CE].

.

.

84, High-High Volume Alarm

Use Function 84 to enter the High-High Volume
Alarm.

High-high volume alarm
9241.60 gl

Enter the number of gallons that will activate the
alarm and press [ENT.].

.

.

184, Low-Low Volume Alarm

Use Function 184 to enter the Low-Low Volume
Alarm.

Low-low volume alarm
924.16 gl

Enter the number of gallons that will activate the
alarm, and press [ENT.].

.

.

81, Set Up Relay [HI, LO]

The X76CTM has 4 user programmable relays. The
relays can be set up to respond to alarm condi-
tions, or be controlled by commands in user
scripts. The name, logic, and time-out can be set
for every relay. To program a relay, use Function 81
and the [HI] and [LO] key.

Set up relay
Relay 1