4 technical specifications – Hochiki FB-1 User Manual

Page 19

Advertising
background image

ESP FIREbeam – Installation Manual

Page 19 of 19

 2011 Hochiki Europe (UK) Ltd

2-3-0-1340/ISS2/DEC11

4 Technical

Specifications

Electrical Specifications

Supply Voltage

17 to 41 Vd.c.

Supply Current

3.5mA (constant current) in all operational states

Constant Current

17mA (constant current) in fast commissioning

Environmental Specifications

Temperature

-10°C to +55°C

Humidity

10 to 95% RH Non-condensing

Ingress Protection Index

IP65 when suitably mounted and terminated

Mechanical Specifications

Beam Head

180mmH x 155mmW x137mmD, Weight 1.1Kg

Controller

185mmH x 120mmW x 62mmD, Weight 0.55g

40KIT80 Mid-Range Reflector

293mmH x293mmW x 5mmD, Weight 0.8Kg

80KIT100 Long Range Reflector

394mmH x 394mmW x 5mmD, Weight 1.8Kg

Adapter (mounts the Beam Head onto unistrut)

270mmH x 250mmW x 5mmD, Weight 0.6g

Optical Specifications

Optical Wavelength

870nm

Maximum Angular Alignment

±5°

Maximum Angular Misalignment

Beam Head ±0.3°, Reflector ±2° (static not auto-aligning)

Operational Specifications

Protection
Range

ESP FIREBEAM

Standard Product 5 to 40 metres

40KIT80

Mid-Range Reflector Kit 40 to 80 metres

80KIT100

Long Range Reflector Kit 80 to 100 metres

Alarm Sensitivity Levels

25%(1.25dB) to 50%(3dB) in 1%(0.05dB) increments (default 35% (1.87dB))

Alarm Condition

Obscuration drops to below pre-defined sensitivity level. Time to Alarm Condition
adjustable 2 to 30 seconds in 1 second increments (default 10 seconds)

Alarm Indication

Controller Status – FIRE, Controller Red Flashing LED, Head Red Flashing LED,
Alarm Relay Change Over (CO) Contact Rating 2A @ 30 VDC

Test/Reset Features

Beam test function by controller. Alarm latching/auto-reset selectable (default
auto-reset). Alarm reset in latching mode by controller reset function, removing
power for >5 seconds, apply 12 to 24 VDC to reset connections in Beam Head.

Fault Sensitivity Level

90%

Fault Condition

Obscuration drops to below the fault sensitivity level within 1 second Power Down
or Supply Voltage < 9 VDC. Commissioning modes, Pre-Alignment and Auto
Alignment. Beam turned off during Beam Maintenance. Time to Fault Condition
adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds)

Fault Indication

Controller Status – FAULT, Controller Yellow Flashing LED 1 Second, Head
Yellow Flashing LED 1 Second, Fault Relay Change Over (CO) Contact Rating
2A @ 30 VDC

Normal Condition

Obscuration level is above the Alarm sensitivity level, Controller Status –
NORMAL, Controller Green Flashing LED, Programmable on/off, Head Green
Flashing LED Programmable on/off

Auto-align/Beam
Contamination Compensation

Auto-align during normal operation if obscuration drops below 90% for the
duration of the align time set (doesn’t effect normal operating mode)
Beam Contamination Compensation 4 hour monitoring. Compensation data
available at the controller