1

Distance and Position Guidelines

These guidelines are recommendations only and it is important that you refer to your appropriate governing
standards at all times.

When positioning your ESP FIREbeam there are important factors that you should consider, mainly what distance
you are covering and the optimal position in the building.

1.1 Distance

The standard ESP FIREbeam is suitable for distances of 5m to 40m to the reflector. If you require 40m to 80m you
will need to use the mid range reflector extension kit. For ranges of 80m to 100m you will require the long range
reflector extension kit.

1.1.1

5 to 40 metres - The Standard ESP FIREbeam

The standard ESP FIREbeam comes boxed with the head unit, low level controller, one reflector, 3mm
allen key and quick start installation guide, this should be used for distances over 5m and up to 40m.

1.1.2

40 to 80 metres - The Standard ESP FIREbeam + Mid Range 40 to 80m Kit

For distances of 40 to 80 metres you will need to use the standard ESP
FIREbeam and a mid range extension kit (the mid range kit comes with
a backing plate and 3 extra reflectors, you will need to add the reflector
from the standard kit to the mid range kit with the screws provided).

1.1.3

80 to 100 metres - The Standard ESP FIREbeam + Long Range 80 to 100m Kit

For distances of 80 to 100 metres you will need to use the standard
ESP FIREbeam and a long range extension kit (the long range kit
comes with a backing plate and 8 extra reflectors, you will need to add
the reflector from the standard kit to the long range kit with the screws
provided).