FIRElink-400 Air Sampling System – Installation Manual

© 2010 Hochiki Europe (UK) Ltd

9-5-0-346/ISS4/OCT10

Setting this function to

Yes

puts the detector into automatic flow limit setup mode. This takes a few

minutes to set the flow fault thresholds based on the current flow rates.

1.1.1 Airflow Monitoring (Display / Numeric - Address 001-127)

Setup Menu > Air Flow

There are separate

Sensor pipe

,

Flow low

,

Flow high

and

Flow pipe

parameters for each

pipe 1 to 4 on the detector. For example,

Flow pipe 1

indicates the current airflow rate for pipe 1.

Sensor pipe 1

to

Sensor pipe 4

are used to enable or disable flow sensing on the specified

pipe inlet of the detector. If any pipe inlets are unused, set the relevant flow sensor function for the pipe
inlet to

No

to avoid unwanted flow faults.

Flow low

is the level below which airflow needs to be reduced to trigger a fault reading (which may

indicate a blocked pipe) and

Flow high

is the level above which airflow needs to increase to trigger a

fault indication (which may indicate a loose or damaged inlet pipe).

Flow low

and

Flow high

parameters are automatically set up on initial power-up or when

Flow

setup

is selected (see section 231156696.01.1.1 “Flow Setup (Yes/No - Address 001-127)” on page

21).

The airflow rates

Flow pipe 1

to

Flow pipe 4

are for display purposes only and cannot be

changed.

1.1.1 Chart Log Recording Rate (Numeric - Address 000-127)

Setup Menu > Miscellaneous

This function controls how frequently the detector and alarm level or flow rates are stored in the Standard
Detector or Command Module internal chart recorder log.

The chart log recording rates are as follows:

Setting

Type

Storage Interval

Time per Division on Chart Log

0

Detector Output

1 second

10 seconds

1

Detector Output

5 seconds

50 seconds

2

Detector Output

12 seconds

2 minutes

3

Detector Output

30 seconds

5 minutes

4

Detector Output

1 minute

10 minutes

5

Detector Output

2 minutes

20 minutes

6

Detector Output

5 minutes

50 minutes

7

Detector Output

10 minutes

100 minutes

8

Detector Output

20 minutes

200 minutes

9

Detector Output

50 minutes

500 minutes

10

Flow Recording

1 second

10 seconds

11

Flow Recording

5 seconds

50 seconds