Hochiki FIRElink-400CM User Manual

Page 47

Advertising
background image

FIRElink-400 Air Sampling System – Installation Manual

Page 47 of 58

© 2010 Hochiki Europe (UK) Ltd

9-5-0-346/ISS4/OCT10

1.1.1 Non Fault Tolerant Serial Configuration

9.3

Connecting a Command Module to an Addressable Fire
Panel

When a Command Module is being used to manage one or more detectors (the maximum limit is 127)
then a Addressable Programmable Interface Card (FIRElink-APIC) may be used to decode detector
status information in the Command Module and relay to the Fire Panel via the Addressable Bus 1 and
Bus 2 terminal block connections (see section 185619544.01.1.1 “Command Module Terminal Block
Connections” on page 34).

In this configuration only one interface is required and all detector information is available through this
interface, one address per device.