HTP ELP-199 User Manual

Page 19

Advertising
background image

19

LP-294 REV. 2.20.14

Figure 5

– Single Boiler with Zone Valves, DHW Priority, and Outdoor Reset – Primary/Secondary -

NOTES:

1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes.
2. All closely spaced tees shall be within 4 pipe diameters center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The minimum

pipe size for connecting a SuperStor indirect water heater is 1”

5. The minimum

pipe size for connecting an Elite Plus is 1.25”

6. Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used with circulator
flanges as an alternative.
7. A mixing valve is recommended if the DHW temperature is set above the factory setting of 119

o

F.

8. Piping shown is Primary/Secondary. System flow (secondary loop) must be greater than the boiler’s primary loop flow.
9. Install a minimum of 12 diameters of straight pipe upstream of all circulators.

Advertising
This manual is related to the following products: