K. fill and purge heating system – HTP ELP-199 User Manual

Page 26

Advertising
background image

26

LP-294 REV. 2.20.14


2. For zoned systems, flush each zone separately through a purge valve. (If purge valves and isolation valves are not already installed,
install them to properly clean the system.)

3. Flush system until water runs clean and you are sure piping is free of sediment.

*NOTE: It is recommended you clean heat exchanger at least once a year to prevent lime scale buildup. Follow the maintenance
procedure to clean the heat exchanger in the Maintenance Section of this manual.

Test/replace freeze protection fluid
1.

For systems using freeze protection fluids, follow fluid manufacturer’s instructions to verify inhibitor level and that other fluid

characteristics are satisfactory.

2. Freeze protection fluid must be replaced periodically due to degradation of inhibitors over time. Follow all fluid manufacturer
instructions.

Piping components

Heating system piping:
Water boiler system piping MUST be sized per technical pipe requirements listed in Table 8 and Table 9. Reducing pipe size can
restrict flow rate through the water boiler, causing inadvertent short cycling and poor system performance.

Check valves:
Field supplied. Check valves are recommended for installation as shown in Piping Details.

Water boiler isolation valves:
Field supplied. Full port ball valves are required. Failure to use full port ball valves could result in a restricted flow rate through the water
boiler.

Mixing valve:
Field supplied. A mixing valve is recommended when storing domestic hot water above 115°F.

Unions:
Field supplied: Recommended for boiler serviceability. DO NOT USE DIELECTRIC UNIONS!
ONLY BRASS, COPPER, OR STAINLESS STEEL.


Pressure relief valve:
Factory supplied on boiler. The pressure relief valve is sized to ASME specifications. Storage tank may require additional relief valves
depending on local codes.

MINIMUM PIPE SIZES

ELP-110

1” NPT or Copper

ELP-199

1 ¼” NPT or Copper

Table 10

K. FILL AND PURGE HEATING SYSTEM

1. Attach the hose to balance and purge hose connector or drain valve and run hose to nearest drain.

2. Close the other side of the balance and purge valve or shut off valve after the drain.

3. Open the first zone balance and purge or drain valve to let water flow out of the hose. If zone valves are used, open the valves one at
a time manually.

NOTE:

You should check zone valve manufacturer’s instructions prior to opening valves manually, so as not to damage the zone valve.


4. Manually operate fill valve regulator. When water runs out of the hose, you will see a steady stream without bubbles. Close the
balance and purge valve or drain to stop the water from flowing. Disconnect the hose and connect it to next zone to be purged.

5. Repeat this procedure for additional zones (one at a time).

For installations that incorporate standing iron radiation and systems with manual vents at the high points, follow the previous section
and, starting with the nearest manual air vent, open the vent until water flows out. Then close the vent. Repeat the procedure, working
your way toward the furthest air vent. It may be necessary to install a basket strainer in an older system where larger amounts of
sediment may be present. Annual cleaning of the strainer may be necessary.

Advertising
This manual is related to the following products: