IAI America PCON-CY User Manual

Page 99

Advertising
background image

89

6. Parameter Settings

z Enable Function (No.42 FPIO)

Whether to enable or disable the deadman switch function on the ANSI-type teaching pendant is set in Parameter No. 42.
* The ANSI-type teaching pendant is currently under development.

Setting

Enable (Use)

0

Disable (Do not use)

1

The factory setting is “1” [Disable].

z Home Check Sensor Input Polarity (No.43 AIOF)

The home check sensor is not included in the standard specification, but it can be installed as an option.
This parameter need not be changed in normal conditions of use. To change the factory-set mode, change the value of
Parameter No. 43.

Definition of settings:

0 (Standard specification; no sensor)
1 (Use the home check sensor, and the sensor polarity conforms to “contact a” logic)
2 (Use the home check sensor, and the sensor polarity conforms to “contact b” logic)

[Explanation of operation]
[1] When a homing command is issued, the actuator moves until it contacts a mechanical end, upon which a home check

sensor signal is detected.

[2] Next, the actuator reverses its direction and stops at the home position.
[3] If the home check sensor signal has changed its signal state, the controller determines that the homing was completed

successfully. If the signal state has not changed, the controller recognizes “position deviation.” Accordingly, the controller
generates a “home sensor non-detection error” and outputs an alarm signal.

Mechanical end

Power input position

Home position

Home check sensor