IDEC SG2 Type 2 Hand & Body User Manual

Page 6

Advertising
background image

A

Keep the receiver in a steady position and set the emitter until the yellow LED (

SYNC) is OFF.

This condition shows the effective alignment of the first beam (synchronisation beam).

B

Rotate the emitter, pivoting on the lower optics axis, until the yellow LED (

LAST) is OFF.

NOTE: Ensure that the green LED (

NORMAL OP.) is steady ON.

C

Delimit the area in which the green LED (

) is steady through some micro adjustments - for the first

and then for the second unit - so to have the maximum alignment (4) and then place both units in the
centre of this area.

D

Fix the two units firmly using brackets.

Verify that the green LED (

) on the RX unit is ON and beams are not interrupted, then verify that

the red LED turns ON if even one single beam is interrupted (

, condition where an object has

been detected).

This verification shall be made with the special cylindrical “Test Piece” having a size suitable to the
resolution of the device used.

E

Switch OFF and ON the device in standard operating mode.

The alignment level is monitored also during device normal operation mode via display (see chapter 7.2
on the manual inside of the attached CD-ROM).
Once the curtain has been aligned and correctly fastened, the display signal is useful both to check the
alignment and show a change in the environmental conditions (occurrence of dust, light disturbance and
so on) via signal level monitoring.



DIAGNOSTICS FUNCTION

The operator can visualise the operating condition of the light curtains thanks to a one-digit display
positioned on both the RX and TX unit.
SG2-E also has four LEDs on the RX unit and two LEDs on the TX unit. The figure below shows all
signalling LEDs modes: OFF, ON and BLINKING.
















4

The operator can evaluate the main causes of the system stopping or failure using the 7-segment display
and LEDs used to visualise the functions. For Receiver:

Function

Status

Meaning

LED

DIGIT

Alignment

Check “ALIGNMENT TABLE”. For more detailed
information refer to the Instruction manual inside
the CD-ROM




TEST
(red ON)

Light curtain being tested, the OSSD status must
be OFF

Emission
(OSSD ON)
(green ON)

Light curtain working and in normal operating
conditions

Interruption
(OSSD OFF)
(red ON)

Light curtain working and in safety block
conditions.

Interlock
Beams free
(red ON
yellow ON)

Interlock curtain waiting for restart. OSSD status
must be OFF

Interlock
Beams interrupted
(red ON
yellow ON)

Light curtain interlocked, OSSD status must be
OFF

Signal level

Minimum (1

bar)

Medium (2

bars)

Maximum (3 bars)

Normal operation

EDM enabled

EDM function is selected



Function

Type

Check and repair

LED

DIGIT

OSSD error
(red ON)

Check OSSD connections. Make sure that they
are not in contact with one another or with the
supply cables, then Reset. If the failure continues
contact DATASENSOR

Internal error
(red ON)

Switch OFF and switch ON the power supply
circuit. If the failure continues contact
DATASENSOR

Optical error
(red ON)

Reset. If the failure continues contact
DATASENSOR

EDM error
(red ON)

Check EDM connections and lines. If the failure
continues contact DATASENSOR

Restart selection error
(red ON)

Check the man/auto restart connection. If the
failure continues contact DATASENSOR

Error status

No power supply
(LEDs OFF)

Check connections and input voltage value. If the
failure continues contact DATASENSOR





5

LED ON

LED OFF


LED BLINKING