System Sensor FAAST Comprehensive User Manual

Page 20

Advertising
background image

AlArm

level

ThreSholD

hiGh

SenSiTiviTY

ThreSholD

loW

SenSiTiviTY

CurrenT level

Alert

Alert High

Alert Low

Acclimate Alert Level

Action 1

Action 1 High

Action 1 Low

Acclimate Action 1

Level

Action 2

Action 2 High

Action 2 Low

Acclimate Action 2

Level

Fire 1

Fire 1 High

Fire 1 Low

Acclimate Fire 1 Level

Fire 2

Fire 2 High

Fire 2 Low

Acclimate Fire 2 Level

TABle 7. AlArm level BounDArY DeSCripTionS

When creating a new project, the Alarm Delay and Threshold fields contain
default values. These settings may be modified to meet local codes and regula-
tions. To modify these settings, select the field, highlight the value shown and
enter the desired value.

The Alarm Delay fields are set to a default value of zero. To modify this value,
highlight the value and enter the desired value.

In normal operation, the Night mode allows separate start and end times,
which can be set for day, night and weekend operation. To set the Night mode,
highlight the hour and click on the up or down arrows to set the hour. Repeat
for the minute, second and AM/PM settings for both the start and end times.

14. When the information on this screen is complete, select the save icon to

save the changes.

15. Select the Network tab at the top of the window and complete the neces-

sary information for the system, as shown in Figure 7. Be sure that all of
the information selected and entered is in accordance with local codes and
regulations.

The Device Details area contains the serial number of the detector and an
identification number (1 – 255). The user may choose any identification num-
ber within the number range. The serial number is assigned at the factory and
cannot be changed.

For more information see the networking white paper at systemseensor.com/faast.

Tables 9 through 11 provide descriptions of the password and E-mail accounts.
Note that the password character strings are case sensitive. Passwords may be
changed in any of the password fields by typing and confirming a password
once Administrative access has been acquired.

TABle 8. WeB ACCeSS pASSWorD FielD DeSCripTionS

TABle 9. ADminiSTrATor pASSWorD FielD DeSCripTionS

TABle 10. DeviCe e-mAil Server ConFiGurATion FielD
DeSCripTionS

FielD

DeSCripTion

Passcode

User can input up to a 16-character string

Confirm Passcode

User must enter the same character string again to

confirm it

FielD

DeSCripTion

Passcode

Administrator can input up to an 8-character string

Confirm Passcode

User must enter the same character string again to

confirm it

FielD

DeSCripTion

Sender Account

E-mail address from which the device

messages originate

SMTP Server Name

Determine the SMTP server being used and type the

SMTP server name in the field . Contact system admin-

istrator if necessary

The Device Connection area allows the user to choose either DHCP or static IP
addresses for device communication. Choosing the DHCP button deactivates
the IP settings. If a static IP address is selected, enter the IP Address, Subnet
Mask and the Default Gateway fields with the proper information (contact
system administrator if necessary). Primary and Secondary DNS Server ad-
dresses are required if address resolution of the SMTP server is desired.

The E-mail Notification area allows the user to type in up to six E-mail ad-
dresses. These addresses are notified when an the selected event is triggered.
The alarm levels reported to each E-mail address can be chosen by selecting
the appropriate alarm level checkboxes for each address.

16. When the information on this screen is complete, a dialog box appears

asking to transfer the configuration changes to the FAAST device. Select
Yes to begin the download.

17. When the download is complete, the detector automatically resets and

begins to take baseline measurements. At this time the system should be
allowed to run undisturbed for at least five minutes to ensure it calculates
valid air flow and filter monitoring baselines. When the system stabilizes,
the front panel indicators are illuminated, as shown in Figure 8. The par-
ticulate level indicators illuminate along with the Test, Reset and Isolate
buttons. The indicators at the bottom of the display indicate the air flow
through the detector. If the system has normal air flow, these indicators
are illuminated in green, near the center of the display.

18. If the location contains more than one FAAST system, repeat this proce-

dure for each system being commissioned at the location.

re-Configuring or updating a FAAST System
When a FAAST detector is configured, certain pipe network specific param-
eters are erased. During the subsequent power-up, the detector will initial-
ize these parameters for the attached pipe network. Once the parameters
are initialized, the detector will operate using these parameters until the next
configuration change. Therefore, it is imperative that the pipe network be
inspected each time the detector is reconfigured. Perform the following proce-
dure to properly re-commission or update a system.
1. If the system fails to power up and stabilize, re-check that all power wiring

is securely and correctly connected.

2. Apply power to the system and open the PipeIQ application. Make sure that

the PipeIQ application is connected to the detector either through a local
network cable or through an internet network connection to the system.

FiGure 7. neTWorK ConFiGurATion TAB

ASP25-01

SS-400-007 20 E56-3621-003

Commissioning