Faast system validation form (cont.) – System Sensor FAAST Comprehensive User Manual

Page 24

Advertising
background image

SS-400-007 24 E56-3621-003

Commissioning

thReshold

time delay

tRanspoRt times

Day

Alert:

Predicted:

Actual:

Action 1:

Predicted:

Actual:

Action 2:

Predicted:

Actual:

Fire 1:

Predicted:

Actual:

Fire 2:

Night

Alert:

Alarm Outputs Verified:

Yes / No

Action 1:

Fault Outputs Verified:

Yes / No

Action 2:

Isolate Function Verified:

Yes / No

Fire 1:
Fire 2:

Weekend

Alert:
Action 1:
Action 2:
Fire 1:
Fire 2:

Acclimate

Alert:
Action 1:
Action 2:
Fire 1:
Fire 2:

Air Flow Fault
Thresholds

Low:
High:

Air Handling

Yes / No

Duct Sampling

Yes / No

Number of Sample points:

Number of Cabinets:

Conditions:

Temperature:
Humidity:
Other:

As-Built Installation
Drawings Available?

Yes / No

Is the system installed in
accordance with the design?

Yes / No

Is the power supply
installed properly?

Yes / No

Is the pipe network installed
and labeled properly?

Yes / No

Describe any Variations:

Sensitivity:

% Obscuration/ft.:

Detector Address:

Detector Address:

FAAST System Validation Form (CONT.)

Comments: