MOUNTING INDOOR WALL OR CEILING PRODUCTS
1. Attach mounting plate to junction box as shown in Figures 3 and 4. The

mounting plate is compatible with 4-inch square, double gang, and 4-inch oc-
tagon junction boxes (2-wire products may be used with a single gang box).

2. Connect field wiring to terminals, as shown in Figures 1 .
3. If the product is not to be installed at this point, use the paint cover to

prevent contamination of the mounting plate. (For indoor models only)

4. To attach product to mounting plate, remove the paint cover, then hook

tabs on the product housing into the grooves on mounting plate.

5. Then, swing product into position to engage the pins on the product with

the terminals on the mounting plate. Make sure that the tabs on the back
of the product housing fully engage with the mounting plate.

6. Secure product by tightening the single mounting screw in the front

of the product housing. For tamper resistance, the standard captivated
mounting screw may be replaced with the enclosed Torx screw.

SURFACE MOUNT BACK BOX MOUNTING
1. The surface mount back box may be secured directly to the wall or ceil-

ing. Grounding bracket provided if needed.

2. The wall mount box must be mounted with the up arrow pointing up.
3. Threaded knockout holes are provided for the sides of the box for ¾ inch

and ½ inch conduit adapter. Knockout plugs in the back of the box can
be used for ¾ inch and ½ inch rear entry.

4. To remove the ½ inch knockout, we recommend you use a flat head

screwdriver and place the blade along the inner edge and work your way
around the knockout as you strike the screwdriver, as shown in Figure
7. To remove the ¾ inch knockout place the blade of the screwdriver
along the edge and work your way around the knockout as you strike the
screwdriver, as shown in Figure 8.

5. V500 and V700 wiremold raceways are also provided. Use V500 for low

profile applications and V700 for high profile applications.

6. To remove the wire mold knockout turn pliers up, as shown in Figure 9.
7. Attach the mounting plate to the surface mount back box using the four

unpainted screws, as shown in Figure 5 or 6.

8. Follow steps 2-6 of the mounting indoor wall or ceiling products to wire

and attach the product.

+

+

INPUT

FROM

FACP

OR

PRIOR

DEVICE

OUTPUT

TO

NEXT

DEVICE

OR EOL

WIRING DIAGRAMS
FIGURE 1. WIRING 2-WIRE PRODUCTS:

A0367-01

SHORTING SPRING

A0368-00

SBB Shown

FIGURE 2. SHORTING SPRING:

2-wire mounting plate

Models are approved for Wall
and Ceiling installations.

A0453-00

A0454-00

FIGURE 3. WALL MOUNT LF SOUNDER:

FIGURE 4. WALL MOUNT LF SOUNDER/STROBE PRODUCT:

FIGURE 5. WALL MOUNT LF SOUNDER WITH

SURFACE MOUNT BACK BOX:

FIGURE 6. WALL MOUNT LF SOUNDER/STROBE

WITH SURFACE MOUNT BACK BOX

A0455-00

A0456-00

Advertising