System Sensor HR-LF, HW-LF, P2RH-LF and P2WH-LF User Manual

Page 3

Advertising
background image

TABLE 2. 2-WIRE LOW FREQUENCY SOUNDER/STROBE CURRENT DRAW (mA) FOR P2H-LF HIGH CANDELA RANGE SERIES:

Sound Pattern

16–33 Volts DC

16–33 Volts FWR

135 cd

150 cd

177 cd

185 cd

135 cd

150 cd

177 cd

185 cd

Temporal

277

292

325

344

296

309

343

351

Continuous

337

362

387

417

393

395

432

433

TABLE 3. LOW FREQUENCY SOUNDER OUTPUT (dBA) IN REVERBERANT (UL**) AND ANECHOIC ROOM:

Switch
Position

Sound Pattern

8–17.5 Volts**

16–33 Volts**

24 V Nominal Measurements

Reverberant

Anechoic

DC

FWR

DC

FWR

DC

FWR

DC

FWR

1

Temporal

76

76

76

76

76

76

86

86

2

Continuous

80

80

80

80

80

80

90

90

3*

Coded

80

80

80

80

80

80

90

90

*Sounder ratings provided are for continuous voltage as provided by the NAC.
** Minimum dB rating for Operational Voltage Range as per UL 464.

SS-120-006

3 I56-3889-000R

A0459-00

A0460-00

A0461-00

CANDELA SELECTION
Adjust the slide switch on the rear of the product to position the desired can-
dela setting in the small window on the front of the unit. All products meet
the light output profiles specified in the appropriate UL Standards. Refer to
Figures 10-12.
SOUNDER SELECTION
Turn the rotary switch on the back of the product to the desired setting. For
sounder and sounder/strobe products (P2H-LF series), current draws are
listed in Tables 1 and 2. The sound output measurement for each sounder
setting is shown in Table 3.

FIGURE 9. V500 AND V700 WIRE MOLD REMOVAL FOR SURFACE
MOUNT BACK BOX

FIGURE 7. ½ INCH KNOCKOUT REMOVAL FOR SURFACE MOUNT
BACK BOX

FIGURE 8. ¾ INCH KNOCKOUT REMOVAL FOR SURFACE MOUNT
BACK BOX

TABLE 1. SOUNDER CURRENT DRAW (mA) FOR H-LF SERIES:

Position Sound Pattern

8–17.5 Volts

16–33 Volts

DC

FWR

DC

FWR

1

Temporal

191

262

138

166

2

Continuous

292

384

138

208

3

Coded

292

388

153

205

NOTE: In position 3, temporal coding must be provided by the NAC. If the
NAC voltage is held constant, the sounder output will remain constantly on.
Coded ratings provided are for continuous voltage. Position 3 is not available
on 2-wire low frequency sounder/strobe products.

Advertising