System Sensor Horns, Strobes and Horn Strobes User Manual

Page 3

Advertising
background image

TABLE 4. 2-WIRE HORN/STROBE CURRENT DRAW ( ) FOR P2 AND PC2 STANDARD CANDELA SERIES:

DC Input

8–17.5 Volts

16–33 Volts

15 cd

15/75 cd

15 cd

15/75 cd

30 cd

75 cd

95 cd

110 cd

115 cd

Temporal High

137

147

79

90

107

176

194

212

218

Temporal Medium

132

144

69

80

97

157

182

201

210

Temporal Low

132

143

66

77

93

154

179

198

207

Non-temporal High

141

152

91

100

116

176

201

221

229

Non-temporal Medium

133

145

75

85

102

163

187

207

216

Non-temporal Low

131

144

68

79

96

156

182

201

210

FWR Input
Temporal High

136

155

88

97

112

168

190

210

218

Temporal Medium

129

152

78

88

103

160

184

202

206

Temporal Low

129

151

76

86

101

160

184

194

201

Non-temporal High

142

161

103

112

126

181

203

221

229

Non-temporal Medium

134

155

85

95

110

166

189

208

216

Non-temporal Low

132

154

80

90

105

161

184

202

211

TABLE 5. 2-WIRE HORN/STROBE CURRENT DRAW ( ) FOR P2 AND PC2 HIGH CANDELA RANGE SERIES:

Sound Pattern

16–33 Volts Volts DC

16–33 Volts Volts FWR

135 cd

150 cd

177 cd

185 cd

135 cd

150 cd

177 cd

185 cd

Temporal High

245

259

290

297

215

231

258

265

Temporal Medium

235

253

288

297

209

224

250

258

Temporal Low

232

251

282

292

207

221

248

256

Non-temporal High

255

270

303

309

233

248

275

281

Non-temporal Medium

242

259

293

299

219

232

262

267

Non-temporal Low

238

254

291

295

214

229

256

262

TABLE 6. HORN OUTPUT ( BA) IN UL REVERBERANT ROOM:

Switch
Position

Sound Pattern

dA

8–17.5 Volts**

16–33 Volts**

24 V Nominal Measurements

Reverberant

Anechoic

DC

FWR

DC

FWR

DC

FWR

DC

FWR

1

Temporal

High

78

78

84

84

88

88

99

98

2

Temporal

Medium

75

75

80

80

86

85

96

96

3

Temporal

Low

71

71

76

76

81

79

94

89

4

Non-temporal

High

82

82

88

88

93

92

100

100

5

Non-temporal

Medium

78

78

85

85

90

89

98

98

6

Non-temporal

Low

73

74

81

81

86

84

96

92

7*

Coded

High

82

82

88

88

93

92

101

101

8*

Coded

Medium

78

78

85

85

90

89

97

98

9*

Coded

Low

74

75

81

81

85

83

96

92

*Horn & 4-wire Horn/Strobe only. ** Minimum dB rating for Operational Voltage Range as per UL 464.

mA

d

mA

D690-03-00

3 I56-2769-018R

FIGURE 4. WIRING 2-WIRE PRODUCTS:

+

+

INPUT

FROM

FACP

OR

PRIOR

DEVICE

OUTPUT

TO

NEXT

DEVICE

OR EOL

A0367-01

FIGURE 5. WIRING 4-WIRE PRODUCTS:

+

INPUT

FROM

FACP OR

PRIOR

STROBE

INPUT FROM

FACP OR PRIOR HORN

+

+

+

OUTPUT

TO NEXT

STROBE

OR EOL

OUTPUT TO NEXT

HORN OR EOL

A0366-00

FIGURE 6. SHORTING SPRING:

SHORTING SPRING

A0368-00

For 4-Wire installations, terminals 1, 2, and 3 connect to the strobe; terminals
4 and 5 connect to the horn. The horn and strobe circuits must be wired in-
dependently, and each circuit must be terminated with the appropriate EOL
device. Removal of a notification device will result in an open circuit indica-
tion on the strobe loop.
NOTE: A shorting spring is provided between terminals 2 and 3 of the mount-
ing plate to enable wiring checks after the system has been wired, but prior
to installation of the final product. This spring will automatically disengage
when the product is installed, to enable supervision of the final system. Only
available on indoor products(non K-series).

Advertising