System Sensor CO1224 User Manual

Co1224 carbon monoxide detector

Advertising
background image

D250-03-00

1

I56-2874-001

CO1224
Carbon Monoxide Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

NOTICE: This manual shall be left with the owner/user of
this equipment.
WARNING: This product is intended for use in ordinary indoor
locations of dwelling units, including homes, residential buildings,
hotels, schools, dormitories, and day care centers. It is not intended
for use in industrial factories or commercial parking garages.

General Description

• Listed to UL standard 2075
• 4 wire, system monitored
• Local sounder
• Low current draw
• Alarm relay, Form C
• Trouble relay, Form A
• Dual LED’s
• Test/Hush button
• SEMS wiring terminals
• Mount to single gang electrical box or surface mount to wall

or ceiling

• Optional drywall anchors included

Figure 1. Alarm Location Diagram:

Specifications

Electrical Specifications
System Voltage

Nominal:

12/24 VDC

Min:

10 VDC

Max:

33 VDC

Avg. Standby Current:

20 mA

Max Alarm Current:

40 mA (75 mA test)

Alarm Contact Ratings:

30 VDC @ 0.5 A

Trouble Contact Ratings:

30 VDC @ 0.5 A

Audible Signal (temp 4 tone):

85 dBA min. in alarm (at 10ft)

Max. Start-up Capacitance:

20 uF

Physical Specifications
Operating Temperature Range:

0° to 40°C (32° to 104°F)

Operating Humidity Range:

22 – 90% %RH

Length:

5.1˝

Width:

3.3˝

Height:

1.3˝

Weight:

7 oz

Wire Gauge Acceptance:

14-22 AWG

Table 1. Detector Operation Modes:

Operation

Mode

Green

LED

Red

LED

Sounder

Normal

(standby)

Blink 1

per minute

-

-

Alarm

-

Blink in

temp 4*

pattern

Sound in

temp 4*

pattern

*Temp 4 pattern is repeated pattern of four short indications fol-
lowed by a five second pause.
When the detector has been in alarm for 30 minutes the alarm
signal will be given once every minute.
If ambient conditions return to normal, the detector will self-re-
store out of alarm and into Normal (standby) mode.
Hush feature: If required, the audible alarm can be silenced for
5 minutes by pushing the button marked “Test/Hush”. The red
alarm light will continue to flash in temp-4 pattern. If carbon
monoxide is still present after the 5 minute hush period, the au-
dible alarm will sound. The hush facility will not operate at levels
above 350 ppm (parts per million) carbon monoxide.
Trouble feature: When the sensor supervision is in a trouble con-
dition (such as a sensor that has been tampered with), the detec-
tor will send a trouble signal to the panel. The detector must then
be replaced.
End of Life Timer feature: When the detector has reached the
end of its life, the trouble contact will open. This indicates that
the CO sensor inside the detector has passed the end of its life
and must be replaced. This detector’s lifespan is approximately
six years from the date of manufacture. Refer to Detector Replace-
ment on page 3.
Per UL 2075, it is mandatory that a trouble signal be sent to the
panel upon CO cell trouble or cell end of life. Refer to Figure 4
for wiring of the trouble relay.

LIVING

ROOM

BEDROOM

BEDROOM

BEDROOM

KITCHEN

TO
BR

CLOSED

DOOR

BASEMENT

GARAGE

CARBON MONOXIDE ALARM
LOCATION FOR MULTI-LEVEL RESIDENCE