[8] FIELD WIRING INSTALLATION GUIDELINES
All wiring must be installed in compliance with the National Electrical Code
and the local codes having jurisdiction. Proper wire gauges should be used.
The conductors used to connect smoke detectors to control panels and acces-
sory devices should be color-coded to prevent wiring mistakes. Improper con-
nections can prevent a system from responding properly in the event of a fire.

For signal wiring, (wiring between interconnected detectors or from detectors
to auxiliary devices), it is recommended that single conductor wire be no
smaller than 18 gauge.

Smoke detectors and alarm system control panels have specifications for al-
lowable loop resistance. Consult the control panel manufacturer’s specifica-
tions for the total loop resistance allowed for the particular control panel being
used before wiring the detector loop.

[8.1] WIRING INSTRUCTIONS
The D4240 detectors are designed for easy wiring. The housing provides a
terminal strip with clamping plates. The D4S housing provides 4 wiring ter-
minals with clamping plates. Wiring connections are made by sliding the bare
end of the wire under the plate, and tightening the clamping plate screw. See
Figure 7 on page 5 for system wiring.
[8.2] SENSOR 2 INSTALLATION/WIRING
The power board is capable of controlling a second housed sensor. The second
sensor, model D4S, can be wired to the power board per the following:

1. Connect wires to the four wire terminals in the corner of the D4S sensor

housing designated as Tamper (Y,Y), +R, and –B. Route wires through the
conduit openings in the sensor housing and D4240 power board housing.

2. Connect the opposing ends of the wires to the terminal connections

marked “Sensor 2” on the Power board. See Figure 6 for reference. En-
sure that wires are connected to the appropriate terminal locations. A
No. 0 or 1 phillips screwdriver should be used for terminal connection.
The tamper terminals are not polarity sensitive.

3. Adjust the middle dip switch on the power board to indicate (2) sensors

as shown in Figure 6.

4. The D4S can only be used with new InnovairFlex models and is not com-

patible with previously sold detectors.[9] Unit Configuration:

[9] UNIT CONFIGURATION
A three position Dip Switch is included on the D4240 in order to configure
the setup of the unit. One switch is used to determine it there are one or two
sensors connected to the Power Board. The second switch selects an instanta-
neous or 7-minute tamper Delay. A tamper Condition indicates that the cover
of the sensor Housing has been removed or has not been secured properly.
The third switch is used to turn the Shutdown On Trouble feature on or off.
With this feature turned On, the Aux relay will switch states when a Trouble
Condition occurs.
*Trouble is indicated when the Supervisory Relay, switches state-Termi-
nals 3 and 14 are open in a Trouble Condition
Causes of a Trouble Condition may be:

• Unit loses Power

• Cover Tamper Feature times out

• Wiring Problems between the Sensor and the Power Board

• Mismatch between number of sensors connected to the Power Board and

the Dipswitch setting

HIGH

LOW

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

TO SAMPLING TUBE

TO EXHAUST TUBE

DIFFERENTIAL

PRESSURE

TRANSMITTER

MODEL #607-01

15 TO 36

VDC SUPPLY

1000 OHM 5%

1 WATT RESISTOR

VOLT METER FLUKE

MODEL 87 OR

EQUIVALENT

+

FIGURE 5. PROCEDURE FOR VERIFYING AIR FLOW LESS THAN 500 FPM:

H0163-01

FIELD SELECTABLE

DIP SWITCHES

TEST/RESET

BUTTON

POWER

BOARD LED 2

SENSOR

LEDs

GROUND

SCREW

SENSOR #1

TERMINALS

D4240

CO-LOCATED

WIRING TERMINALS

24V

AC
/DC
, 10

24V

AC
/DC
, 9

AU
X OUT +,

19

AU
X OUT -,

20

INT/

AU
X-

, 1

INT+

, 12

ALARM,

15

R

TEST

, 11

R RESET

, 2

AC
C

-

AC
C

+

240 VAC

B

-

R

+

Y

Y

B

-

R

+

Y

Y

TAMPER

TAMPER

SENSOR 1

SENSOR 2

OFF/ON

TRBL SHUTDN

1/2 SENSORS

7/0 MIN

TMPR DEL

AY

7,

NO

18,
C

AUX B

8,

NC

17,
NO

AUX A

6,

C

16,
NC

14,
N0

3,

C

13,
NC

5,

NO

SUP

ALARM

4,

C

D4S

SENSOR ONLY

SENSOR #2

TERMINALS

TAMPER

Y Y R B

Y Y R B

+ –

TAMPER

+ –

SENSOR 2

D4240

D4S

POWER

BOARD LED 1

240

VAC INPUT

VARISTOR

24 VAC/

DC INPUT

24V AC/DC, 10

24V AC/DC, 9

AUX OUT +, 19

AUX OUT -, 20

INT/AUX-, 1

INT+, 12

ALARM, 15

R TEST, 11

R RESET, 2

ACC -

ACC +

7, NO

18, C

8, NC

17, NO

6, C

16, NC

14, N0

3, C

13, NC

5, NO

4, C

SS-300-022

4 I56-3936-003R

H0557-16

FIGURE 6. OPTIONAL SENSOR 2 CONFIGURATION AND WIRING:

Advertising