System Sensor RTC User Manual

System Sensor Equipment

Advertising
background image

F440-02-00

1

I56-648-03

RTC Remote Test Coil Kit for use

with the B404B and B404BT Bases

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

NOTICE: This manual should be left with the owner/user
of this equipment.

General Description

The System Sensor Model RTC Remote Test Coil Kit allows
for the remote testing of duct detectors using the B404B or
B404BT bases that are installed in inconvenient or difficult-
to-reach locations. Model RTC can be installed in almost
any convenient location and can be attached to a standard
2" X 4" electrical box.

The National Fire Protection Association has published
standards and practices for the installation and use of this
device. As a result, System Sensor recommends that the in-
staller be familiar with these standards and practices, local
codes, and any special requirements of the authority hav-
ing jurisdiction.

RTC Contents

1 RTS451 Remote Test Station
2 #8 x 1/4" pan head screws for mounting bracket
1 Test Coil/Replacement Ring
1 Screw Pack (2 mounting Assembly screws)
1 Jumper with spade lugs
1 M02-04 Test Magnet

Installation
Installation of the Model RTC consists of attaching the test
station to the mounting surface, mounting the test coil on
the detector, and routing the necessary wiring between
them. This installation procedure assumes that the
associated detector base is already installed and ready for
operation.

Figure 1:

A78-1995-00

Specifications
Dimensions:

6.6"H x 2.75"W x 1.5"D

Weight:

.11 lb.

Power Requirements
Alarm LED:

2.8 - 32 VDC, 10 mA max.

Test Coil:

15.5 - 32 VDC, 95 mA max.

Total Current:

105 mA max.

Test Switch:

10 VA @ 32 VDC

Reset Switch:

10 VA @ 32 VDC

Alarm Response Time:

40 seconds max.

Operating Temperature Range:

-10

°

C to 60

°

C (14

°

F to 140

°

F)

Humidity:

95% RH, noncondensing