System Sensor 2012H Photoelectronic User Manual

Page 2

Advertising
background image

D100-55-00

2

I56-733-10

Figure 2: Recommended smoke detector protection for single-

floor residence with more than one sleeping area:

BEDROOM

SMOKE DETECTORS FOR
MINIMUM PROTECTION

SMOKE DETECTORS FOR
MORE PROTECTION AND
REQUIRED IN NEW CONSTRUCTION

BEDROOM

BEDROOM

LIVING ROOM

DINING

ROOM

KITCHEN

FAMILY ROOM

A78-1171-02

NFPA 72, Chapter 2, Section 2-2.1.1.1 states as follows: “Smoke detectors
shall be installed outside of each separate sleeping area in the immediate
vicinity of the bedrooms and on each additional story of the family living
unit, including basements and excluding crawl spaces and unfinished at-
tics. In new construction, a smoke detector also shall be installed in each
sleeping room.”
The above NFPA standard is a minimum requirement for smoke detec-
tor installation. For better protection, we also require the installation
of a smoke detector inside every bedroom in existing construction.

Install a minimum of two smoke detectors in any household, no
matter how small it is.

Put a smoke detector in the hallway outside of every separate bed-
room area.
(See Figure 1.) A minimum of two detectors are required in
homes with two bedroom areas. (See Figure 2.)

Put a smoke detector on every level of a multi-level residence. (See
Figure 3.)

Install basement detectors on the ceiling at the bottom of the basement
stairwell. (See Figure 3.)

Figure 3: Recommended smoke detector protection for a multi-

level residence:

BEDROOM

BEDROOM

BEDROOM

LIVING

ROOM

KITCHEN

BASEMENT

GARAGE

SMOKE DETECTORS FOR MINIMUM PROTECTION

SMOKE DETECTORS FOR MORE PROTECTION AND
REQUIRED IN NEW CONSTRUCTION

A78-1171-03

Install detectors on the ceiling as close to the center of the room as
possible. If this is not practical, install it on the ceiling no closer than 4
inches (10 cm) from any wall or corner. (See Figure 4.)

If wall-mounting is permitted by local and state codes, and ceiling
mounting is not practical, install detectors on an inside wall between 4
and 6 inches (10 and 15 cm) from the ceiling. (See Figure 4.)

Figure 4: Recommended smoke detector mounting locations:

BEST LOCATION
ACCEPTABLE LOCATION

DEAD AIR

SPACE

BEST IN CENTER

OF CEILING

NO CLOSER THAN 4

" (10 cm)

FROM SIDE WALL

MOUNT ON WALL

AT LEAST 4

" (10 cm)

FROM CEILING

NO MORE

THAN 6

" (15 cm)

FROM CEILING

A78-1171-04

Put detectors at both ends of a bedroom hallway if the hallway is more
than 30 feet (9 meters) long. In addition, large rooms will require more
than a single detector if the room is over 900 square feet.

Rooms or areas that do not have smooth ceilings, or which have short,
transom-type walls coming down from the ceiling require additional
detectors.

Install second-floor detectors on the ceiling at the top of the first-to-
second floor stairwell. Be sure no door or other obstruction blocks the
path of smoke to the detector.

In rooms with sloped, peaked, or gabled ceilings, install detectors 3
feet (0.9 meter) measured down on the slant from the highest point of
the ceiling. See Figure 5.

Figure 5: Recommended smoke detector location in rooms with

sloped, gabled or peaked ceilings:

HORIZONTAL

DISTANCE

FROM PEAK

3 FEET

(.9M)

A78-1171-05

Where Smoke Detectors Should NOT Be Installed

In or near areas where combustion particles are normally present
such as kitchens; in garages
where there are particles of combustion
in vehicle exhausts; near furnaces, hot water heaters, or gas space
heaters. Install detectors at least 20 feet
(6 meters) away from kitch-
ens and other areas where combustion particles are normally
present.

On the ceiling in rooms next to kitchens where there is no transom
between the kitchen and these rooms. Instead, install the smoke detec-
tor on an inside wall, furthest from the kitchen (See Figure 6). Be sure
not to install smoke detectors within 4" of the ceiling or any corner or
more than 6" from the ceiling.

Figure 6: Recommended smoke detector locations to avoid air
streams with combustion particles:

CORRECT

AIR RETURN

BEDROOM

BATH

BEDROOM

LIVING

ROOM

INCORRECT

KITCHEN

STOVE

AIR INLET

A78-1171-06

In damp or very humid areas, or next to bathrooms with showers.
The moisture in humid air can enter the sensing chamber as water va-
por, then cool and condense into droplets that cause a nuisance alarm.
Install detectors at least 5 feet (1.5 meters) away from bathrooms.

In very cold or very hot rooms or areas. Operating temperature of the
smoke detector is 40

°

F to 100

°

F (4

°

C to 38

°

C).

In dusty, dirty, or insect-infested areas. Dust and dirt can build up on
the detector’s sensing chamber and make it overly sensitive, or can
block openings to the sensing chamber and keep the detector from
sensing smoke.

Near fresh air inlets or returns or excessively drafty areas. Air con-
ditioners, heaters, fans, and fresh air intakes and returns can drive
smoke away from smoke detectors, making the detectors less effective.

In dead air spaces at the top of a peaked ceiling or wall/ceiling inter-
sect. Dead air may prevent smoke from reaching a detector.

Near fluorescent light fixtures. Install detectors at least 10 feet (3
meters) away from such light fixtures.

Installation Requirements
Warning: Electrical Shock Hazard. Turn off power at the main fuse box
or circuit breaker to the area of detector installation before beginning in-
stallation procedures.

Mount detector to a 4-inch octagonal junction box only. Mount the 12

Advertising
This manual is related to the following products: