System Sensor 2112_24AITR Photoelectronic User Manual

Installation and maintenance instructions

Advertising
background image

D200-85-00

1

I56-1241-03R

2112/24AITR

Photoelectronic Smoke Detector with

Fixed Heat and Integral Temp-3 Sounder

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Specifications
Diameter:

5.5 inches (140 mm)

Height (including mounting bracket):

2.05 inches (52 mm)

Weight:

7.5 oz. (210 g)

Operating Temperature Range:

32° to 100°F (0° to 38°C)

Operating Humidity Range:

10% to 93% Relative Humidity, Noncondensing

Latching Alarm:

Reset by momentary power interruption

Audible Signal:

85 dBA minimum when in alarm or with supply polarity reversed

Heat Sensor:

135°F Fixed Temperature Electronic Thermistor

Electrical Ratings
System Voltage (nominal):

12 or 24 VDC

Minimum:

10 VDC

Maximum:

35 VDC

Maximum Ripple Voltage:

30% of nom. Voltage (peak to peak)

Standby Current:

50 µA maximum

Alarm Current:

49 mA typical, 60 mA max. at 12V
57 mA typical, 65 mA max. at 24V

Reset Voltage:

0.8 VDC minimum

Reset Time:

1.0 second maximum

Start-up Time:

30 seconds maximum (after 60 sec. reset)

EOL Relay:

A77-716B, 12/24 VDC
Note: Relay changes only when the thermal alarm state is reached

Alarm Initiation and Auxiliary Relay:

1A @ 30 VAC

Contact Ratings, Resistive Load:

1A @ 30 VDC

Special Considerations:

Due to the built-in temporal pattern, use these detectors only with a non-coded power supply.

Figure 1. Wiring diagram for the 2112/24AITR detector:

A78-2336-16

Before Installing
Please thoroughly read the System Sensor manual I56-407, Guide for
Proper Use of System Smoke Detectors,
which provides detailed informa-
tion on detector spacing, placement, zoning, wiring, and special applica-
tions. Copies of this manual are available at no charge from System
Sensor.

NOTICE: This manual shall be left with the owner/user of this equipment.

IMPORTANT: This detector must be tested and maintained following
NFPA 72 requirements. The detector should be cleaned at least once a
year.

IMPORTANT: OBSERVE POLARITY

As with all sounder models, polarity must be observed on the power connections.

OPTIONAL CLASS A WIRING

EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER

EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V

POWER

TO

DETECTORS

UL LISTED

COMPATIBLE

CONTROL

PANEL

INITIATING

LOOP

+

P

W

R

A
U
X

P

W

R

A
U
X

+
+

A
A

NC

C

NO

+
+

A
A

NC

C

NO

ALARM
CONTACT

ALARM
CONTACT

(OPTIONAL)
RELEASING

DEVICE

NC

COMMON

NO

(OPTIONAL)
RELEASING

DEVICE

NC

COMMON

NO