System Sensor 2112_24AITR Photoelectronic User Manual

Page 3

Advertising
background image

D200-85-00

3

I56-1241-03R

Put a smoke detector on every level of a multi-level residence. (See

Figure 3.)

Install basement detectors on the ceiling at the bottom of the basement
stairwell. (See Figure 3.)

Figure 3: Recommended smoke detector protection for a multi-
level residence:

• Install detectors on the ceiling as close to the center of the room as

possible. If this is not practical, install it on the ceiling no closer than
4 inches (10 cm) from any wall or corner. (See Figure 4.)

If wall-mounting is permitted by local and state codes, and ceiling

mounting is not practical, install detectors on an inside wall between
4 and 6 inches (10 and 15 cm) from the ceiling. (See Figure 4.)

Figure 4: Recommended smoke detector mounting locations:

Put detectors at both ends of a bedroom hallway if the hallway is more
than 30 feet (9 meters) long. In addition, large rooms will require more
than a single detector if the room is over 900 square feet.

Rooms or areas that do not have smooth ceilings, or which have short,
transom-type walls coming down from the ceiling require additional
detectors.

Install second-floor detectors on the ceiling at the top of the first-to-
second floor stairwell. Be sure no door or other obstruction blocks the
path of smoke to the detector.

In rooms with sloped, peaked, or gabled ceilings, install detectors 3
feet (0.9 meter) measured down on the slant from the highest point of
the ceiling. See Figure 5.

Figure 5: Recommended smoke detector location in rooms with
sloped, gabled or peaked ceilings:

Where Smoke Detectors Should NOT Be Installed

In or near areas where combustion particles are normally present
such as kitchens; in garages
where there are particles of combustion
in vehicle exhausts; near furnaces, hot water heaters, or gas space
heaters. Install detectors at least 20 feet
(6 meters) away from
kitchens and other areas where combustion particles are normally
present.

HORIZONTAL

DISTANCE

FROM PEAK

3 FEET

(.9M)

;;;;;;;

;;;;;;;

;;;;;;;

;;;;;;;

;;;;;;;

;;;;;;;

BEST LOCATION
ACCEPTABLE LOCATION

DEAD AIR

SPACE

BEST IN CENTER

OF CEILING

NO CLOSER THAN 4" (10 cm)

FROM SIDE WALL

MOUNT ON WALL

AT LEAST 4" (10 cm)

FROM CEILING

NO MORE

THAN 6" (15 cm)

FROM CEILING

BEDROOM

BEDROOM

BEDROOM

LIVING

ROOM

KITCHEN

BASEMENT

GARAGE

SMOKE DETECTORS FOR MINIMUM PROTECTION

SMOKE DETECTORS FOR MORE PROTECTION AND
REQUIRED IN NEW CONSTRUCTION

On the ceiling in rooms next to kitchens where there is no transom
between the kitchen and these rooms. Instead, install the smoke detec-
tor on an inside wall, furthest from the kitchen (See Figure 6). Be sure
not to install smoke detectors within 4" of the ceiling or any corner or
more than 6" from the ceiling.

Figure 6: Recommended smoke detector locations to avoid air
streams with combustion particles:

In damp or very humid areas, or next to bathrooms with showers.
The moisture in humid air can enter the sensing chamber as water
vapor, then cool and condense into droplets that cause a nuisance
alarm. Install detectors at least 5 feet (1.5 meters) away from bath-
rooms.

In very cold or very hot rooms or areas. Operating temperature of the
smoke detector is 32°F to 100°F (0°C to 38°C).

In dusty, dirty, or insect-infested areas. Dust and dirt can build up on
the detector’s sensing chamber and make it overly sensitive, or can
block openings to the sensing chamber and keep the detector from
sensing smoke.

Near fresh air inlets or returns or excessively drafty areas. Air con-
ditioners, heaters, fans, and fresh air intakes and returns can drive
smoke away from smoke detectors, making the detectors less effective.

In dead air spaces at the top of a peaked ceiling or wall/ceiling inter-
sect. Dead air may prevent smoke from reaching a detector.

Near fluorescent light fixtures. Install detectors at least 10 feet (3
meters) away from such light fixtures.

Installation Requirements
Warning: Electrical Shock Hazard. Turn off power at the main fuse box
or circuit breaker to the area of detector installation before beginning
installation procedures.

Remove power from the control unit or initiating device circuits before
installing detectors.

1. Wire the plug-in screw terminal block per Figure 1 and plug the ter-

minal block into the detector.

2. Align the arrows on the detector with the arrows on the mounting

bracket.

3. Turn the detector clockwise in the mounting bracket until it clicks into

place.

4. After all detectors have been installed, apply power to the control unit

or initiating device circuits.

5. Test the detector as described in TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities the system is in operation.

Dust covers are an effective way to limit the entry of dust into smoke
detector sensing chambers. However, they may not completely prevent air-
borne dust particles from entering the detector. Therefore, System Sensor
recommends the removal of detectors before beginning construction or
other dust producing activity. Be sure to remove dust covers from any sen-
sors that were left in place during construction as part of returning the sys-
tem to service.

CAUTION

WARNING

CORRECT

AIR RETURN

BEDROOM

BATH

BEDROOM

LIVING

ROOM

INCORRECT

KITCHEN

STOVE

AIR INLET

A78-1171-03

A78-1171-04

A78-1171-05

A78-1171-06

Advertising