System Sensor B401BH-2 User Manual

B401bh-2 sounder bases

Advertising
background image

D450-00-00

1

I56-2816-003R

B401BH-2
Sounder Bases

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

BEfORE INSTALLINg
Please thoroughly read the, System Smoke Detector Application Guide, which
provides detailed information on detector spacing, placement, zoning, wiring,
and special applications. Copies of this manual are available from System Sen-
sor. NFPA 72 and NEMA guidelines should be observed.

NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with these bases must be tested and main-
tained regularly following NFPA 72 requirements. The detector used with
these bases should be cleaned at least once a year.
gENERAL DESCRIpTION
Model B401BH-2 sounder bases is intended for use with System Sensor 400
Series plug-in sensor heads in conventional 2-wire plug-in systems. Refer to
systems manuals for the maximum allowable number of units per loop. The
B401BH-2 requires an external 24VDC (nominal) supply with reverse polarity
capability. The connections of the external supply (terminals 1 and 2) and the
initiating loop (terminals 3, 4, and 5) are isolated in the B401BH-2 to prevent
electrical interaction between them.

A loop of horns can be made to sound by reversing the polarity of the external
supply.
NOTE: When the associated system is NOT used as a supplementary evacua-
tion system, the external 24VDC supply must be treated as a component of the
main power supply system with the result that it falls under the requirements
of NFPA 72.
B401BH-2 TERMINALS
No. Function
1

External Supply Positive (+)

2

External Supply Negative (–)

3

Negative (–) V

4

Positive (+) V In

5

Positive (+) V Out

Terminals 3, 4, and 5 are used for the communication/initiating circuit.
INSTALLATION WIRINg gUIDELINES
All wiring must be installed in compliance with the National Electrical Code
and all applicable local codes and any special requirements of the authority
having jurisdiction, using the proper wire size. The conductors used to con-
nect smoke detectors to control panels and accessory devices should be color-
coded to reduce the likelihood of wiring errors. Improper connections can
prevent a system from responding properly in the event of a fire.

SpECIfICATIONS
Base Diameter:

6 inches (152 mm)

Base Height (less base and sensor):

0.75 inches (19mm)

Weight:

0.32 lb. (145 g)

Operating Temperature Range:

14° to 140°F (–10° to +60°C)

Operating Humidity Range:

10% to 95%, non-condensing

Electrical Ratings
Voltage:

17 to 32 VDC

Standby Current:

1.0 mA maximum

Alarm Current:

15 mA maximum

Maximum Ripple Voltage:

10% of supply voltage

Start-up Capacitance:

200 µF

Horn Input Current Requirement:

600 µA maximum

Sound Output:

Greater than 90 dBa measured in anechoic room at 10 feet (3 meters),

24 volts. 85 dBa minimum measured in UL reverberant room.

Sounder Delay Time:

0.75 to 5.7 sec

For signal wiring (the wiring between interconnected detectors), it is recom-
mended that the wire be no smaller than AWG 18. However, the screws and
clamping plate in the base can accommodate wire sizes up to AWG 12. The
use of twisted pair wiring or shielded cable for the power (+ and –) loop is
recommended to minimize the effects of electrical interference on the initiat-
ing loop.

Begin electrical connections by stripping about 3/8” insulation from the end
of the wire. Then, slide the bare end of the wire under the clamping plate and
tighten the clamping plate screw. Break the wire at each terminal to ensure
that the connections are supervised, as shown in Figure 2.
fIgURE 2.

DO NOT loop the wire under the clamping plate.

Check the zone wiring of the detector base before the detector heads are
installed. Perform continuity, base polarity, and dielectric tests on the wiring.

Smoke detectors and alarm system control panels have specifications for al-
lowable supervision current. Consult the control panel manufacturer’s speci-
fications for the total loop current supervision allowed for the control panel
being used before wiring the detector loops.

I56-28

16-00

3R

fIgURE 1. TERMINAL LAyOUT:

C0471-00

C0473-00