Screws, Detector base box, Shorting spring – System Sensor B401BH-2 User Manual

Page 2

Advertising
background image

CLASS A OPTIONAL WIRING

UL

LISTED COM

P

A

TIBLE

CONVENTIONAL

CONTROL

P

ANEL

EXTERNA

L

24V

SUPPL

Y

CLASS A OPTIONAL WIRING

UL

LISTED EOL

RESISTOR

UL

LISTED

EOL

RELAY

24V

(+) INIT.

(−) INIT.

(−)POWER

(+)POWER

4 5

2 1

3

4 5

2 1

3

4 5

2 1

3

fIgURE 3. TypICAL WIRINg LAyOUT:

SCREWS

(NOT SUPPLIED)

DETECTOR

BASE

BOX

(NOT SUPPLIED)

SHORTING

SPRING

fIgURE 4. MOUNTINg TO AN ELECTRICAL BOx:

C0503-01

C0956-01

System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for this air duct smoke
detector. No agent, representative, dealer, or employee of the Company has the authority
to increase or alter the obligations or limitations of this Warranty. The Company’s obliga-
tion of this Warranty shall be limited to the replacement of any part of the product which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns Department, RA

Please refer to insert for the Limitations of Fire Alarm Systems

THREE-yEAR LIMITED WARRANTy

#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
the malfunction and suspected cause of failure. The Company shall not be obligated to
replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.

WIRINg INSTRUCTIONS
The shorting spring in the base will disengage automatically when the detec-
tor head is removed from the base.
DO NOT remove the shorting spring since it reengages as the detector head is
turned into the base, completing the circuit.

A typical wiring for a two-wire conventional system is shown in Figure 3. Re-
fer to this diagram as needed while wiring the base into the system.

NOTE: Figure 3 shows external 24V supply polarity when
the loop system is in standby (NOT alarming).

MOUNTINg
NOTE:
It is recommended that the base be completely wired before mounting.
See Figure 4. Attach the base directly to an electrical box using the screws
supplied with the box. Then, use the plastic screw covers, supplied with the
base, to cover the screws.

The sounder base is 1.1 inches (28 mm) deep. Electrical boxes must be 4 inches
(102 mm) square by at least 1-

1

/

2

inches (38 mm) deep; 2-

1

/

8

inches (54 mm)

is recommended.
TESTINg
Before testing, notify the proper authorities that the smoke detector system is un-
dergoing maintenance and that the system will be temporarily out of service. Dis-
able the zone or system undergoing maintenance to prevent unwanted alarms.

Detectors and bases must be tested after installation and following periodic
maintenance.

Test the B401BH-2 as follows:

1. Test the conventional detector head following the procedure in its man-

ual. The B401BH-2 should sound approximately 0.75 to 5.7 seconds after
the detector alarms.

2. Reverse the polarity of the external 24 VDC supply. This should cause

every base in the loop to sound after approximately 0.75 to 5.7 seconds.

D450-00-00

2

I56-2816-003R

©2010 System Sensor

Advertising