System Sensor RRS-MOD User Manual

Page 2

Advertising
background image

D500-44-00

2

I56-2203-005

NOTE: Please refer to Figures 5 and 6 for Ademco Vista panels and Figures 7 and 8 for DSC Power 832 panels.

S0101-01

S0102-00

S0103-01

Figure 1. 2-Wire sYsTem Triggered From aLarm/BeLL ouTPuT:

Figure 2. 4-Wire sYsTem Triggered From aLarm/BeLL ouTPuT:

Figure 3. 2-Wire sYsTem Triggered From aLarm reLaY ConTaCT:

EOL

OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)

OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)

+

UL LISTED

ALARM

CONTROL

PANEL

2–WIRE

INITIATING

DEVICE

CIRCUIT

PURPLE

T+

+

+

AUX POWER

YELLOW

IN+

ORANGE

IN–

RED

PWR+

BLACK

PWR–

BROWN

OUT+

WHITE

OUT–

1 + IN

2 + OUT

3 - IN/OUT

4 RA+

5 RA-

1 + IN

2 + OUT

3 - IN/OUT

4 RA+

5 RA-

+

BELL/

ALARM

CIRCUIT

(positive signal

in alarm state)

EOL

UL LISTED

ALARM

CONTROL

EOL RELAY

(SHOWN ENERGIZED)

PANEL

DETECTOR

POWER

+

+

AUX POWER

OR

DETECTOR

POWER

INITIATING

DEVICE
CIRCUIT

+

BELL/ALARM

CIRCUIT

(positive signal

in alarm state)

PURPLE

T+

YELLOW

IN+

ORANGE

IN–

RED

PWR+

BLACK

PWR–

BROWN

OUT+

WHITE

OUT –

1 + IN

2 + OUT

3 - IN/OUT

4 N.O.

5 C

1 + IN

2 + OUT

3 - IN/OUT

4 N.O.

5 C

ALARM

RELAY

(NO Contact)

UL LISTED

ALARM

CONTROL

PANEL

2–WIRE

INITIATING

DEVICE

CIRCUIT

PURPLE

T+

+

+

AUX POWER

YELLOW

IN+

ORANGE

IN–

RED

PWR+

BLACK

PWR–

BROWN

OUT+

WHITE

OUT–

EOL

OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)

OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)

+

1 + IN

2 + OUT

3 - IN/OUT

4 RA+

5 RA-

1 + IN

2 + OUT

3 - IN/OUT

4 RA+

5 RA-

+

CAUTION

When using the RRS-MOD with model
2WTA-B, do not mix the 2WTA-B with
other model smoke detectors and dry
contact closure devices, including me-
chanical heat detectors, manual pull
stations and waterflow switches. Such
mixing can cause a direct short on the
auxiliary power terminals, damaging the
control panel’s internal circuitry and/or
damaging devices connected to the initi-
ating device circuit.