System Sensor RRS-MOD User Manual

Page 3

Advertising
background image

UL LISTED

ALARM

CONTROL

PANEL

2 – WIRE

SMOKE

ZONE

+

+

AUXILIARY

POWER
OUTPUT

YELLOW

PURPLE

T +

ORANGE

RED

BLACK

BROWN

WHITE

AUXILIARY

RELAY

470
1/2 WATT*

SYSTEM SENSOR
2WTA-B SMOKE
DETECTORS
(UP TO 16 DETECTORS
PER ZONE)

ADEMCO

CONTROL

PANEL

APPCLICABLE

CONTROLS:

5110XM
5140XM

VISTA-32FB

VISTA-100

VISTA-128FB

SYSTEM SENSOR REVERSING

RELAY/SYNCHRONIZATION MODULE (RRS-MOD)

(MOUNT INSIDE CONTROL ENCLOSURE)

NOT REQUIRED ON 5110XM

WHEN 5100XM JUMPER W3 INTACT

TAKE POWER FROM CONTROLS
AUXILIARY POWER OUTPUT ONLY

EOL
2K OHMS

OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)

OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)

+

1 + IN

2 + OUT

3 - IN/OUT

4 RA+

5 RA-

1 + IN

2 + OUT

3 - IN/OUT

4 RA+

5 RA-

+

*470Ω 1/2 WATT RESISTOR NEEDED FOR PANEL TO RESET

ALARM

CIRCUIT

(positive signal
in alarm state)

UL LISTED

ALARM

CONTROL

PANEL

INITIATING

CIRCUIT

PURPLE

T+

+

+

AUX POWER

2 -WIRE

YELLOW

ORANGE

RED

BLACK

BROWN

WHITE

BELL/

470
1/2 WATT*

ADEMCO

CONTROL

PANEL

APPCLICABLE

CONTROLS:

VISTA-20
VISTA-40

VISTA-50P

VISTA-32FB

VISTA-100

VISTA-128FB

SYSTEM SENSOR REVERSING

RELAY/SYNCHRONIZATION

MODULE ( RRS-MOD)

(MOUNT INSIDE CONTROL ENCLOSURE)

SYSTEM SENSOR
2WTA-B SMOKE
DETECTORS
(UP TO 16 DETECTORS
PER ZONE)

EOL

2K OHMS

OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)

OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)

+

1 + IN

2 + OUT

3 - IN/OUT

4 N.O.

5 C

1 + IN

2 + OUT

3 - IN/OUT

4 RA+

5 C

+

*470Ω 1/2 WATT RESISTOR NEEDED FOR PANEL TO RESET

D500-44-00

3

I56-2203-005

S0104-00

Figure 4. 4-Wire sYsTem Triggered From aLarm reLaY ConTaCT:

UL LISTED

ALARM

CONTROL

PANEL

DETECTOR

POWER

+

+

AUX POWER

OR

DETECTOR

POWER

INITIATING

DEVICE
CIRCUIT

+

ALARM
RELAY
(NO Contact)

PURPLE

T+

YELLOW

IN+

ORANGE

IN–

RED

PWR+

BLACK

PWR–

BROWN

OUT+

WHITE

OUT–

EOL

EOL RELAY

(SHOWN ENERGIZED)

1 + IN

2 + OUT

3 - IN/OUT

4 N.O.

5 C

1 + IN

2 + OUT

3 - IN/OUT

4 N.O.

5 C

S0105-02

Figure 5. ConneCTing 2WTa-B smoke deTeCTors To ademCo ConTroLs using rrs-mod moduLe Triggered From BeLL/aLarm CirCuiT:

S0106-02

Figure 6. ConneCTing 2WTa-B smoke deTeCTors To ademCo ConTroLs using rrs-mod moduLe Triggered From auxiLiarY reLaY:

ConneCTion diagrams WiTh ademCo VisTa PaneLs
The connection diagrams enclosed show how to connect the 2WTA-B model smoke detector to the Vista panels using the System Sensor polarity reversal relay
module (RRS-MOD). Please make sure that the smoke detectors are connected properly to the zones specified in the wiring diagrams for proper operation of the
smoke detectors.

Programming information:

• The supervisory feature for the bell cir-

cuit must be turned off. See applicable
control manual for procedure.

RRS-MOD Configuration:

• Set switch on RRS-MOD to “OFF”.

Programming information:

• Program Auxiliary relay to activate on

alarms

• Assign Auxiliary relay as an output for

zones programmed for fire alarm re-
sponse only (Types 9, 16, or 17)

RRS-MOD Configuration:

• Set switch on RRS-MOD to “ON”.

Advertising