System Sensor IM-10 User Manual

Im-10 ten input monitor module

Advertising
background image

Shipped on Board:
(1) Shunt in Class A/B position
(Shipped in Class B position, remove shunt for Class A)

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a
listed compatible system control panel.

COMPONENTS

Following are descriptions of the IM-10 mounting frameworks.
There are two mounting options for IM-10 modules:

• Up to six IM-10 modules can be installed on a CH-6 in a

BB-6 cabinet

• One or two IM-10 modules can be installed in a BB-2 cabinet

Chassis
The CH-6 chassis is used to mount IM-10 modules in a BB-6 cabi-
net. It accommodates up to six IM-10 modules in a single cabinet
row three modules wide and two modules deep.

Figure 1. CH-6 Chassis:

The BB-2 cabinet has a built-in chassis that will accommodate
one or two IM-10 modules.

BEFORE INSTALLING

This information is included as a quick reference installation
guide. Refer to the appropriate control panel installation manual
for detailed system information. If the modules will be installed in
an existing operational system, inform the operator and local au-
thority that the system will be temporarily out of service. Discon-
nect the power to the control panel before installing the modules.
This system contains static sensitive components. Always ground
yourself with a proper wrist strap before handling any circuits so
that static charges are removed from the body. The housing cabi-
net should be metallic and suitably grounded.
NOTICE: This manual should be left with the owner/user of this
equipment.

GENERAL DESCRIPTION

The IM-10 Ten Input Monitor Module is intended for use in an in-
telligent alarm system. Each monitor module is intended to inter-
face between a control panel and normally open contact devices,
such as pull stations. A common SLC input is used for all mod-
ules, and the initiating device loops share a common supervisory
supply and ground. Otherwise, each monitor operates indepen-
dently from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the
first module from 01 to 90. The remaining modules are automati-
cally assigned to the next nine higher addresses. Provisions are
included for disabling a maximum of two unused modules to re-
lease the addresses to be used elsewhere. Each module also has
panel controlled green LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
Included:
(6) 1 x 4 Terminal Blocks (2) 1

1

/

4

″ (32mm) Stand offs

(4) Machine Screws (2) Nuts (3) Shunts (10) 47k Ohm

End of Line Resistors

D500-47-00

1

I56-1797-007

INSTALLATION AND MAINTENANCE INSTRUCTIONS

IM-10
Ten Input Monitor Module

SPECIFICATIONS
Normal Operating Voltage:

15–32 VDC

Stand-By Current:

3.5 mA

Alarm Current:

60 mA (assumes all ten LEDs solid on)

Temperature Range:

32°F to 120°F (0°C to 49°C)

Humidity:

10 to 93% Non-condensing

Dimensions:

6.8˝H x 5.8˝W x 1.25˝D

Accessories:

CH-6 Chassis; BB-6 Cabinet; BB-2 Cabinet

Wire Gauge:

12-18 AWG

Maximum IDC Wiring Resistance:

40 Ohms

Maximum IDC Voltage:

12 VDC

Maximum IDC Current:

1 mA

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com