System Sensor IM-10 User Manual

Page 3

Advertising
background image

D500-47-00

3

I56-1797-007

Figure 6b. Installation of IM-10 module in front chas-
sis position:

2

3

1

Step 1: Insert the bottom edge of the IM-10 module down into a

front slot of the chassis.

Step 2: Carefully swing the upper edge of the board towards the

back of the chassis until it touches the 1

1

/

4

˝ (31.75mm)

standoffs installed on the rear module.

Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instruc-

tions in this manual.

WIRING

NOTE: All wiring must conform to applicable local codes, ordi-
nances, and regulations.
1. Install module wiring in accordance with the job drawings and

appropriate wiring diagrams.

2. All wiring to the IM-10 is done via terminal blocks. In order to

properly make electrical connections strip approximately

1

/

4

˝

of insulation from the end of wire, sliding the bare end of the
wire under the clamping plate screw.

3. Set the address on the modules per the job drawing. Use the

rotary code switches to set the address of the first module (be-
tween 01 and 90).

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device

must accept any interference received, including interference that may cause undesired operation.

NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to pro-

vide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed

and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a

particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the

user is encouraged to try to correct the interference by one or more of the following measures:

– Reorient or relocate the receiving antenna.

– Increase the separation between the equipment and receiver.

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

– Consult the dealer or an experienced radio/TV technician for help.

C0226-00

In Class B operation, the remaining modules are automati-

cally assigned to the next nine higher addresses. For exam-
ple, if the base address switch is set to 28, the next nine
modules will be addressed to 29, 30, 31, 32, 33, 34, 35, 36,
and 37.

The module is shipped in Class B position, remove shunt for

Class A. When operating in Class A, alternate modules are
paired together (+0/+1, +2/+3, +4/+5, +6/+7, +8/+9),
resulting in a total of five modules. For example, if the base
address switch is set to 28, then 30, 32, 34 and 36 will be auto-
matically assigned to the modules while 29, 31, 33, 35 and 37
are available to be used for other modules on the SLC. For Class
A and B operation, DO NOT set the lowest address above 90, as
the other modules will be assigned to nonexistent addresses.

4. A shunt is provided to disable a maximum of two unused mod-

ules in Class B operation and one unused module in Class A
operation. Modules are disabled from the highest address and
work downward. If two modules are disabled, the lowest eight
addresses will be functional, while the highest two will be dis-
abled. For example, in Class B operation, if the shunt for Ad-
dress Disable is placed on “two” and the base switch is set to
28, the modules will be assigned to 28, 29, 30, 31, 32, 33, 34
and 35 while disabling the highest two positions.

NOTE: Place unused shunts on single pin to store on board for

future use.

NOTE: Power must not be applied to the unit when changing

functionality of the shunts.

WIRING NOTES
• Power-limited circuits must employ type FPL, FPLR, or

FPLP cable as required by Article 760 of the NEC.

Advertising