System Sensor CZ-6 User Manual

Cz-6 six zone interface module, Installation and maintenance instructions, Specifications

Advertising
background image

BEFORE INSTALLING
This information is included as a quick reference installation
guide. Refer to the appropriate control panel installation manual
for detailed system information. If the modules will be installed in
an existing operational system, inform the operator and local au-
thority that the system will be temporarily out of service. Discon-
nect the power to the control panel before installing the modules.
This system contains static sensitive components. Always ground
yourself with a proper wrist strap before handling any circuits so
that static charges are removed from the body. The module hous-
ing should also be grounded.
NOTICE: This manual should be left with the owner/user of
this equipment.

D500-49-00

1

I56-1799-005

INSTALLATION AND MAINTENANCE INSTRUCTIONS

CZ-6 Six Zone Interface Module

SPECIFICATIONS

Normal Operating Voltage:

15-32 VDC

Stand-By Current:

2 mA

Alarm Current:

40 mA (assumes all six LEDs solid on)

Temperature Range:

32°F to 120°F (0°C to 49°C)

Humidity:

10 to 93% Non-condensing

Dimensions:

6.8˝H x 5.8˝W x 1.25˝D

Accessories:

CH-6 Chassis; BB-2 Cabinet; BB-6 Cabinet

Wire Gauge:

12-18 AWG

Maximum IDC Wiring Resistance:

25 Ohms

External Power Supply Voltage:

Regulated 24VDC

Ripple Voltage:

0.1 volts RMS maximum

IDC (supervised and power limited)
DC Voltage:

18-28 volts power limited

Frequency:

DC

Current:

90mA per circuit

3825 Ohio Avenue, St. Charles, Illinois 60174

800/736-7672, FAX: 630/377-6495

www.systemsensor.com

DET.

DETECTOR

MODEL

COMP. ID

MANUFACTURER

BASE MODEL

MAX DET.

1151

A

SYSTEM SENSOR

B110LP, B401

20

1451

A

SYSTEM SENSOR

B401, B401B

20

1451DH

A

SYSTEM SENSOR

DH400

20

2151

A

SYSTEM SENSOR

B110LP, B401

20

2451

A

SYSTEM SENSOR

DH400, B401B, B401

20

2451TH

A

SYSTEM SENSOR

B401, B401B

20

5451

A

SYSTEM SENSOR

B401

20

1100

A

SYSTEM SENSOR

N/A

20

1400

A

SYSTEM SENSOR

N/A

20

** 2100AT

A

SYSTEM SENSOR

N/A

20

2100B

A

SYSTEM SENSOR

N/A

20

2100D

A

SYSTEM SENSOR

N/A

20

2100S

A

SYSTEM SENSOR

N/A

20

2100TB

A

SYSTEM SENSOR

N/A

20

2100TD

A

SYSTEM SENSOR

N/A

20

2100TS

A

SYSTEM SENSOR

N/A

20

2300B

A

SYSTEM SENSOR

N/A

20

2300TB

A

SYSTEM SENSOR

N/A

20

2400

A

SYSTEM SENSOR

N/A

20

2400TH

A

SYSTEM SENSOR

N/A

20

* 2W-B

A

SYSTEM SENSOR

N/A

20

* 2W-TB

A

SYSTEM SENSOR

N/A

20

DH100LP

A

SYSTEM SENSOR

N/A

20

* Class B, Style B only
** No Accessory will be supported by 2100AT

GENERAL DESCRIPTION
The CZ-6 Six Zone Interface Module is intended for use in an
intelligent alarm system. Each module provides an interface be-
tween the intelligent alarm system and a conventional alarm sys-
tem loop. A common SLC input is used for all modules, and the
initiating device loops share a common supervisory supply and
ground. Otherwise, each monitor operates independently from the
others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first
module from 01 to 94. The remaining modules are automatically
assigned to the next five higher addresses. Provisions are included
for disabling a maximum of two unused modules to release the
addresses to be used elsewhere. Each module also has panel con-
trolled bicolor LED indicators. The panel can cause the LEDs to
blink, latch on, or latch off.

Compatible Two-wire System Sensor Smoke Detectors for use with CZ-6 with Zone Identifier A

I56-1799-00

5