System Sensor M500DR User Manual

M500dr audio control module, H x 4˝ w x 1, D (mounts to a 4˝ square by 2

Advertising
background image

0

1

2

3

4

9

8

7

6

5

0

TENS

ONES

ADDR

ESS

LOOP

9

8

7

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

D500-38-00

1

I56-1390-001

M500DR Audio Control Module

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Before Installing
This information is included as a quick reference instal-
lation guide. Refer to the control panel installation man-
ual for detailed system information. If the modules will
be installed in an existing operational system, inform the
operator and local authority that the system will be tempo-
rarily out of service. Disconnect power to the control panel
before installing the modules.
NOTICE: This manual should be left with the owner/user
of this equipment.
General Description
M500DR Audio Control Modules are intended for use in in-
telligent, two-wire systems, where the individual address of
each module is selected using the built-in rotary switches.
This module is used to select either one of two separate au-
dio signals, then connect it to a speaker circuit. Wiring to the
speaker circuit is supervised, and status is reported to the
panel as NORMAL, OPEN, or SHORT CIRCUIT. The M500DR
has two pairs of output termination points available for fault-
tolerant wiring, and does not require external non-polarized
capacitors. There is a panel-controlled LED indicator.
Compatibility Requirements
To ensure proper operation, this module shall be connected
to compatible system control panels only.
Mounting
This module mounts directly to 4˝ square electrical boxes (see
Figure 2A). The box must have a minimum depth of 2

1

/

8

˝.

Flush mounted electrical boxes (SMB500) are available.
Wiring
NOTE:
All wiring must conform to applicable local codes,
ordinances and regulations. When using control modules
in nonpower limited applications, the CB500 Module Bar-
rier must be used to meet UL requirements for the separa-
tion of power-limited and nonpower-limited terminals and
wiring. The barrier must be inserted into a 4˝x 4˝x 2

1

/

8

˝

junction box, and the control module must be placed into
the barrier and attached to the junction box (Figure 2A).

Figure 1. Controls
and Indicators:

Figure 2A. Module
mounting with
barrier:

C0219-01

Figure 2B. Isolated Quadrant:

C0217-01

C0218-01

Specifications
Normal Operating Voltage:

15 to 32 VDC

Maximum Current Draw:

6.5 mA (LED on)

Average Operating Current:

390µA (LED flashing)

External Supply Voltage Maximum:
(between Terminals T2/T3 or T4/T5) 70.7 Volts RMS, 50W
Temperature Range:

32˚F to 120˚F (0˚C to 49˚C)

Humidity:

10% to 93% Non-condensing

Dimensions:

4

1

/

2

˝ H x 4˝ W x 1

1

/

4

˝ D (Mounts to a 4˝ square by 2

1

/

8

˝ deep box.)

Accessories:

SMB500 Electrical Box; CB500 Barrier

The power-limited wiring must be placed into the isolated
quadrant of the module barrier (Figure 2B).
1. Install module wiring in accordance with the job draw-

ings and appropriate wiring diagrams (Figures 3-4).

2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer),

as shown in Figure 2A.

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

ISOLATED

QUADRANT

0

1

2

3

4

9

8

7

6

5

0

TENS

ONES

ADDR

ESS

LOOP

9

8

7

6

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

9
8
7
6
5

4

3

2

1

0

0

1

2

3

4

5 6

7 8 9

TENS

ONES

ADDRESS

LOOP

10

7 8

6

5

4

3

2

9

I56-1390-001

Advertising