Figure 3. Typical wiring for speaker supervision and switching, NFPA Style Y:

Figure 4. Typical wiring for speaker supervision and switching, NFPA Style Z:

WARNING

All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed)
state during shipping. To ensure that the switch contacts are in their correct state, modules must be made to communicate
with the panel before connecting circuits controlled by the module.

C0671-02

C0672-02

Three-Year Limited Warranty

System Sensor warrants its enclosed product to be free from defects in materi-

als and workmanship under normal use and service for a period of three years

from date of manufacture. System Sensor makes no other express warranty

for the enclosed product. No agent, representative, dealer, or employee of the

Company has the authority to increase or alter the obligations or limitations

of this Warranty. The Company’s obligation of this Warranty shall be limited

to the replacement of any part of the product which is found to be defective

in materials or workmanship under normal use and service during the three

year period commencing with the date of manufacture. After phoning System

Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization

number, send defective units postage prepaid to: System Sensor, Returns

Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please

include a note describing the malfunction and suspected cause of failure.

The Company shall not be obligated to replace units which are found to be

defective because of damage, unreasonable use, modifications, or alterations

occurring after the date of manufacture. In no case shall the Company be

liable for any consequential or incidental damages for breach of this or any

other Warranty, expressed or implied whatsoever, even if the loss or damage

is caused by the Company’s negligence or fault. Some states do not allow the

exclusion or limitation of incidental or consequential damages, so the above

limitation or exclusion may not apply to you. This Warranty gives you specific

legal rights, and you may also have other rights which vary from state to state.

FROM PANEL OR

(+)

(–)

TO NEXT

(+)

(–)

DEVICE

(+)

(–)

(–)

(+)

(–)

(+)

TO NEXT MODULE

LAST MODULE MUST RETURN

WIRES FOR SUPERVISION

MODULE POLARITIES ARE

SHOWN IN ALARM

CONNECT MODULES TO LISTED COMPATIBLE

BRANCH CIRCUITS

BREAK WIRE TO ENSURE

SUPERVISION OF CONNECTIONS.

DO NOT LOOP WIRE AROUND TERMINALS.

ALL WIRING SHOWN IS SUPERVISED.

(+)

CONTROL PANELS ONLY

PREVIOUS DEVICE

47 K EOL
RESISTOR
A2143-00

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

SIGNAL LINE CIRCUIT (SLC)

(–)

AUDIO AMPLIFIER B

70.7 Vrms MAX.

WHEN A 70.7V AUDIO AMPLIFIER IS USED, TERMINALS 0 AND 1 ARE POWER LIMITED,
WHILE TERMINALS 2-9 ARE NONPOWER LIMITED. IN THIS CASE THE CB500 BARRIER
IS REQUIRED. OTHERWISE, ALL TERMINAL WIRING IS POWER LIMITED.THE CB500
INCLUDES A LABEL INDICATING WHICH TERMINALS ARE NONPOWER LIMITED.
THIS LABEL MUST BE PLACED ADJACENT TO THE NAMEPLATE LABEL,
PRESENT ON THE MODULE HOUSING.

AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.

AUDIO AMPLIFIER A

70.7 Vrms MAX.

(+)

(–)

9
8
7
6
5

4

3

2

1

0

0

1

2

3

4

5 6

7 8 9

TENS

ONES

ADDRESS

LOOP

0

1

2

3

4

5 6

7 8 9

FROM PANEL OR

(+)

(–)

TO NEXT

(+)

(–)

DEVICE

(+)

(–)

(–)

(+)

(–)

(+)

TO NEXT MODULE

LAST MODULE MUST RETURN

WIRES FOR SUPERVISION

MODULE POLARITIES ARE

SHOWN IN ALARM

CONNECT MODULES TO LISTED COMPATIBLE

BRANCH CIRCUITS

BREAK WIRE TO ENSURE

SUPERVISION OF CONNECTIONS.

DO NOT LOOP WIRE AROUND TERMINALS

ALL WIRING SHOWN IS SUPERVISED.

(+)

CONTROL PANELS ONLY

PREVIOUS DEVICE

EOL RESISTOR
IS INTERNAL AT
TERMINALS 8 & 9

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

SIGNAL LINE CIRCUIT (SLC)

(–)

AUDIO AMPLIFIER B

70.7 Vrms MAX.

WHEN A 70.7V AUDIO AMPLIFIER IS USED, TERMINALS 0 AND 1 ARE POWER LIMITED,
WHILE TERMINALS 2-9 ARE NONPOWER LIMITED. IN THIS CASE THE CB500 BARRIER
IS REQUIRED. OTHERWISE, ALL TERMINAL WIRING IS POWER LIMITED.THE CB500
INCLUDES A LABEL INDICATING WHICH TERMINALS ARE NONPOWER LIMITED.
THIS LABEL MUST BE PLACED ADJACENT TO THE NAMEPLATE LABEL,
PRESENT ON THE MODULE HOUSING.

AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM.

AUDIO AMPLIFIER A

70.7 Vrms MAX.

(+)

(–)

9
8
7
6
5

4

3

2

1

0

0

1

2

3

4

5 6

7 8 9

TENS

ONES

ADDRESS

LOOP

0

1

2

3

4

5 6

7 8 9

Advertising