System Sensor M500M-4-20 User Manual

System Sensor Equipment

Advertising
background image

M500M-4-20
4-20mA Analog Input Module

Before InstAllIng
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.
generAl DescrIptIon
The M500M-4-20 4-20mA Analog Input Module is intended for use in intel-
ligent, two-wire systems, where the individual address of each module is
selected using the built-in rotary switches. This module allows intelligent pan-
els to interface and monitor two-wire or three-wire sensors, that produce a
4-20mA signal output. It transmits the status (normal, open, or alarm) of one
sensor back to the control panel. The M500M-4-20 has a panel controlled LED
indicator. Only one sensor can be connected to the M500M-4-20.
coMpAtIBIlIty requIreMents
To ensure proper operation, this module shall be connected to a listed compat-
ible system control panel only.
MountIng
The M500M-4-20 mounts directly to 4-inch square electrical boxes (see Figure
1). The box must have a minimum depth of 2

1

/

8

inches. Surface mounted

electrical boxes (SMB500) are available from System Sensor.
WIrIng
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for powerlimited wiring only.

1. Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in

Figure 1.

specIfIcAtIons
SLC

Normal Operating Voltage:

15 to 32 VDC

Maximum Current Draw:

9.3 mA (LED on)

Average Operating Current:

1 mA (LED flashing)

External Supply

Normal Operating Voltage:

24 VDC Nominal

Standby Current:

10 mA

Maximum Current:

510 mA

Initiating Device

Maximum Current:

500 mA

Temperature Range:

10˚C to 60˚C

Humidity:

10% to 95% Non-condensing

Dimensions:

4

1

/

2

˝ H × 4˝ W × 1

1

/

4

˝ D (Mounts to a 4˝ square by 2

1

/

8

˝ deep box.)

Accessories:

SMB500 Electrical Box

fIgure 1. MoDule MountIng:

C0959-00

SS-460-000

1

I56-3070-002

I56-3

07

0-00

2

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

InstAllAtIon AnD MAIntenAnce InstructIons

Advertising