TERMINAL WIRING MUST

BE POWER LIMITED.

DO NOT LOOP WIRE UNDER TERMINALS.

BREAK ALL WIRE RUNS TO PROVIDE

SUPERVISION OF CONNECTIONS.

M500M-4-20

MODULE

TO NEXT

DEVICE

SIGNAL LINE CIRCUIT (SLC) 32

VDC MAX.

TWISTED PAIR

IS RECOMMENDED

FROM PANEL OR

PREVIOUS DEVICE

SLC WIRING

24 VDC POWER

LIMITED

( + ) ( - )

(–) SENSE

(+)

{

TO 4-20mA

2-WIRE DEVICE

24 VDC POWER SUPPLY

ISOLATED, REGULATED,

POWER LIMITED PER

NFPA 70, UL 864 LISTED

FOR FIRE PROTECTION

SIGNALING USE WITH

BATTERY BACKUP.

TO NEXT

MODULE

SS-460-000

2

I56-3070-002

©2008 System Sensor

fIgure 3. 4-20 A MoDule 2-WIre confIgurAtIon:

C1034-01

(+)

(–)

(+)

(–)

(+)

(–)

TERMINAL WIRING MUST

BE POWER LIMITED

TO NEXT

DEVICE

M500M-4-20

MODULE

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

FROM PANEL OR

PREVIOUS DEVICE

SLC

WIRING

( - )

SENSE

( + )

{

TO 4-20mA

3-WIRE

DEVICE

DO NOT LOOP WIRE UNDER TERMINALS.

BREAK ALL WIRE RUNS TO PROVIDE

SUPERVISION OF CONNECTIONS.

24 VDC POWER

LIMITED

( + ) ( - )

24 VDC POWER

SUPPLY ISOLATED,

REGULATED, POWER

LIMITED PER NFPA 70,

UL 864 LISTED FOR

FIRE PROTECTION

SIGNALING USE WITH

BATTERY BACKUP.

TO NEXT

MODULE

C1035-01

fIgure 2. 4-20 A MoDule 3-WIre confIgurAtIon: