System Sensor M500M User Manual

M500m monitor module

Advertising
background image

SS-460-004

1

I56-3855-001

M500M Monitor Module

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

BEfORE INSTALLINg
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.
gENERAL DESCRIpTION
The M500M Monitor Module is intended for use in intelligent, two-wire sys-
tems, where the individual address of each module is selected using the built-
in rotary decade switches. It provides either a 2-wire or 4-wire fault tolerant
initiating circuit for normally open contact fire alarm, supervisory, or security
devices. The module has a panel controlled LED indicator.
COMpATIBILITy REqUIREMENTS
To ensure proper operation, these modules shall be connected to listed com-
patible system control panels only.
fIgURE 1. CONTROLS AND INDICATORS:

C0917-01

SpECIfICATIONS
Normal Operating Voltage:

15 to 32 VDC

Maximum Current Draw:

5.0mA (LED on)

Average Operating Current:

350 μA, 1 communication every 5 seconds, 47k EOL

EOL Resistance:

47K Ohms

Maximum IDC wiring resistance:

40 Ohms

Maximum IDC Voltage:

11 Volts

Maximum IDC Current:

400μA

Temperature Range:

32˚F to 120˚F (0˚C to 49˚C)

Humidity:

10% to 93% Non-condensing

Dimensions:

4

1

/

2

˝ H x 4˝ W x 1

1

/

4

˝ D (Mounts to a 4˝ square by 2

1

/

8

˝ deep box.)

Accessories:

SMB500 Electrical Box

MOUNTINg
The M500M mounts directly to 4-inch square electrical boxes (see Figure 2).
The box must have a minimum depth of 2

1

/

8

inches. Surface mounted electri-

cal boxes (SMB500) are available from System Sensor.
fIgURE 2. MODULE MOUNTINg:

ISOLATED

QUADRANT

C1044-00

WIRINg
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power limited wiring only.

1. Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in

Figure 2.

I56-3855-00

1