System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for the enclosed product.
No agent, representative, dealer, or employee of the Company has the authority to in-
crease or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the replacement of any part of the product which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns Department, RA

fIgURE 3. TypICAL 2-WIRE INITIATINg CIRCUIT CONfIgURATION, NfpA STyLE B:

(+)

(–)

(+)

(–)

(+)

(–)

MONITOR

MODULE

ANY NUMBER OF UL LISTED

CONTACT CLOSURE DEVICES

MAY BE USED. DO NOT MIX FIRE

ALARM INITIATING,

SUPERVISORY, OR SECURITY

DEVICES ON THE SAME MODULE.

TO NEXT

DEVICE

FROM PANEL OR

PREVIOUS DEVICE

47K EOL

RESISTOR

ELR-47K

CONNECT MODULES TO LISTED

COMPATIBLE CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

SHIELDED-TWISTED PAIR

IS RECOMMENDED

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B

POWER LIMITED: 400µA MAX. @ 11 VDC MAX

INSTALL CONTACT CLOSURE DEVICES PER

MANUFACTURER’S INSTALLATION INSTRUCTIONS.

C1051-00

fIgURE 4. TypICAL 4-WIRE fAULT TOLERANT INITIATINg CIRCUIT CONfIgURATION, NfpA STyLE D:

(+)

(-)

(+)

(–)

(+)

(–)

MONITOR

MODULE

TO NEXT

DEVICE

FROM PANEL OR

PREVIOUS DEVICE

CONNECT MODULES TO LISTED

COMPATIBLE CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

SHIELDED-TWISTED PAIR

IS RECOMMENDED

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

ANY NUMBER OF UL LISTED

CONTACT CLOSURE DEVICES

MAY BE USED. DO NOT MIX FIRE

ALARM INITIATING,

SUPERVISORY, OR SECURITY

DEVICES ON THE SAME MODULE.

INSTALL CONTACT CLOSURE DEVICES PER

MANUFACTURER’S INSTALLATION INSTRUCTIONS.

EOL RESISTOR

IS INTERNAL AT

TERMINALS

8 AND 9

C0919-03

ThREE-yEAR LIMITED WARRANTy

#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
the malfunction and suspected cause of failure. The Company shall not be obligated to
replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.