5

cartridge, as it can be damaged when handled. Slide a new filter cartridge into the cap. Twist the cap with the

new filter cartridge onto the probe base until it is tight.

NOTE: It is very important that you operate the PRO-Alert 2791 with a filter cartridge installed at all times.

Failure to do so could damage the leak detector’s components.

Changing the Infrared Cell

WARNING

COMPONENTS MAY BE HOT. TURN OFF DETECTOR AND DISCONNECT POWER ADAPTER CORD

BEFORE REMOVING THE INFRARED CELL DOOR.
The PRO-Alert 2791 infrared (IR) cell is located in the body of the detector. The IR cell is a complete assembly

consisting of a metal tube, connectors and electronic components. The IR cell is not designed to be taken

apart. Doing so will destroy the cell. This specialized IR cell will operate for about 1,000 hours.

The PRO-Alert 2791 will flash all the yellow leak indicators when the IR cell has reached the end of its useful

life. To replace the IR cell:

1. Locate the latch for the IR cell door on the top cover at the rear of the detector.

2. Using a small screwdriver, pull the latch forward and remove the door.

3. Grasp the IR cell according to the directions

printed on its label. Pull it straight out so both ends are

released at the same time.

4. Remove the replacement IR cell from the protective package.

5. Carefully align the male leads and air tubes on the IR cell with the connectors mounted on the circuit board.

Insert the leads into the sockets and push the IR cell straight down.

NOTE: Ensure the lead connectors on the IR cell ends are not bent and the cell is seated tightly.

Removing/Replacing the Power Stick

The PRO-Alert 2791 uses a preassembled power stick.

Remove the battery compartment door on the back of the PRO-Alert 2791 by pressing on both release

buttons on the grip and pulling the door straight out. The power stick is connected to the circuit board via a

miniature electrical connector. Disengage the connector and slide the power stick out of the PRO-Alert 2791.

Slide the new stick into the PRO-Alert 2791 and push the miniature connector on the power stick into the

mating half on the circuit board. Do not bend the circuit board’s connector away from the board. Once the

power stick is in place, close the battery compartment by aligning the two tabs and sliding the door straight in

until it latches. Ensure the wire leads on the power stick are not pinched in the door. Allow 10 hours to fully

charge the new power stick.

Replacement Parts and Accessories

Replacement parts and accessories for your PRO-Alert 2791 are available through the same dealer from

whom you bought the instrument.
12-volt cord with cigarette-lighter plug, 12 ft (3.7 m)

125954

120-volt mains adapter and cord, 6 ft (1.8 m)

125955

230-volt (Euro plug) mains adapter and cord, 6 ft (1.8 m)

125956

230-volt (UK plug) mains adapter and cord, 6 ft (1.8 m)

125957

240-volt mains adapter and cord, 6 ft (1.8 m)

126000

100-volt mains adapter and cord, 6 ft (1.8 m)

125958

Power stick

125922

Replacement infrared cell

125959

Filter cartridges, package of 5

125921

Replacement probe cap

125923

Specifications

Usage

Indoor or outdoor

Optimum sensitivity to R-12 and R-134a

Down to 0.1 oz/yr. (3 g/yr.)

Input voltage range

12 to 16 V(DC)

Input current

500 mA max.

Operating and charging temperature range*

+32 °F to 122 °F (0 °C to +50 °C)

Storage temperature range

+14 °F to +140 °F (-10 °C to +60 °C)

Humidity

95% RH NC max.

Altitude

6500 ft (2000 m)

Pollution degree

2

Overvoltage category

2

Weight (with power cells)

1.28 lb (0.58 kg)

*May be operated for a limited time in lower temperature environments