Standard installation, Installation, 2 standard installation – TREND 963 Installation User Manual

Page 8

Advertising
background image

Installation

3

The use of a dot matrix printer is recommended for alarms. Use of inkjet or laser printers for alarm printing is likely

to cause undesirable results e.g. each line of the alarm on a separate page. A separate printer for graphs and
schematic pages (graphics printer) is recommended. The graphics printer can be connected using a parallel or USB
port. The printer may also be accessed over the office IT network (providing a network card is fitted). This should
be taken into account when specifying the required ports for the PC.

4

963 will also operate on Windows Vista™ Business

4

SP1 and Windows Server 2003

5

SP2 Standard, and Enterprise

with Internet Explorer version 6 SP1.

5

963 will only operate on 32 bit operating systems.

I

f installing 963 on a PC that has a full installation of SQL server earlier than SQL Server 2005 it is necessary to

upgrade to SQL Server 2005.

If the 963 is to communicate with devices on a BACnet network TOPS must also be installed. This installation can
be on the same PC as 963, or on a different PC providing communication is possible between the two over Ethernet.
The installation of TOPS is carried out by a step-by-step installation program. Once installed TOPS must be
licensed, and configured, as described in the 963 Engineering Manual (TE200637).

If 963 is to communicate with BACnet devices using TOPS installed on the same PC the PC must be running
Windows XP, or Windows 2003 SP1.

963 Clients
PCs:
963 Clients may be of any configuration providing they are running TCP/IP networking protocol, and have an
Ethernet card, and have a web browser installed. For full graphics capabilities (graphic mode) Internet Explorer v6.0
or greater, or Firefox 2 (recommended Internet Explorer version 6 or greater) and the SUN JAVA runtime
environment J2SE 5.0 or greater is required. The browser must have JAVA script enabled. Other browsers will
provide a text only display (text mode).

PDAs: PDA’s running Windows Mobile 2003 Second Edition or greater (text mode only).

Smartphones: Nokia 9210i, and smartphones running Window Mobile 5 or greater (text mode only).

Note that the 963 has not been tested with all devices and Trend cannot guarantee a particular device’s
compatibility with 963 Server.

Popup blocking software must be disabled, or configured to allow popups from the 963 Server.

PC Resources
963 is a real time application; installed PCs must have enough free resources to safely run 963 under peak load
conditions. We cannot guarantee system performance if other 3

rd

party software is installed, for example virus

checking software.

2.2 Standard Installation

This section describes the standard installation procedure for installing the 963. This procedure should be suitable
for most installations.

Standard installation:

1. Ensure that the PC meets the system requirements see the 'System Requirements' section of these

instructions for more details.

2. Install the 963 software as described in the 'Install the 963 Software' section of these instructions.
3. Run 963 and licence it as described in the 'Licence 963' section of these instructions.

When the 963 is run for the first time, it displays a password for the System Administrator. This password
MUST be noted, as without this password it will not be possible to gain access to the default program’s
functionality.

4. Connect the GSM modem as described in the 'Connect the GSM Modem' section of these instructions. (963

SMS Direct only).

5. Configure the GSM connection as described in the 'Configure the GSM Connection' section of these

instructions. (963 SMS Direct only).

6. Connect the PC to the Ethernet Network as described in the 'Connect the PC to the Ethernet Network'

section of these instructions.

7. Connect the PC to the IQ network as described in the 'Connect the PC to the IQ Network' section of these

instructions.

8. Check communications as described in the 'Check Communications' section of these instructions.

After the installation is complete it is strongly recommended that the 963 be configured to automatically
archive the database to prevent it becoming to large as described in the 'Configure Automatic Archiving'
section of 963 Engineering Manual (TE200637).

963 Installation Instructions TG201026 Issue 09/01/2009