REV 3 DIGITMR USER’S MANUAL

26

3.5.3. Timing a CLOSE-OPEN Operation Using Contact Channel #1

The CLOSE-OPEN operation of a breaker simulates a condition where a breaker is closed on a
fault. To time a CLOSE-OPEN operation:

a. Start from the “START-UP” menu:

Press the

[1]

key (TIME BRKR) to start a test.

b. The following screen will be displayed:

Press the

[1]

key (NO).

c. The following screen will be displayed:

Press the

[1]

key (WINDOW = 1 SEC) to select the 1-second timing window.

d. The following screen will be displayed:

Press the

[1]

key (Internal Trigger) to select the internal trigger.

e. The following screen will be displayed:

Press the

[4]

key (C-O) to select the CLOSE-OPEN timing operation.

TIMING MODE
1. OPEN 2. CLOSE
3. O-C 4. C-O

5. O-C-O

TRIGGER MODE:

1. Internal Trigger

2. External Trigger

TIMING WINDOW:
1. WINDOW = 1 SEC

2. WINDOW = 10 SEC

3. WINDOW = 20 SEC

INSERTION RESISTOR?

1. NO

2. YES

1. TIME BRKR 04/17/09

2. GET RSLT 10:49:23

3. SET-UP

4. DIAGNOSTICS