Mounting the sw dvi plus switcher, Tabletop use, Rack mounting – Extron Electronics SW DVI Plus Series User Guide User Manual

Page 41: Tabletop use rack mounting

Advertising
background image

SW DVI Plus Series • Reference Information

35

35

35

35

Mounting the SW DVI Plus Switcher

The SW DVI Plus Series switcher can be set on a table, mounted on a rack shelf, or mounted
under a desk, podium, or table.

Tabletop use

Four self-adhesive rubber feet are included with the SW DVI Plus. For tabletop use, attach
one foot at each corner on the bottom of the unit, and place the switcher where desired.

Rack mounting

UL rack mounting guidelines

The following Underwriters Laboratories (UL) guidelines pertain to the safe installation of the
equipment in a rack.

1.

Elevated operating ambient temperature — If the equipment is installed in a closed
or multi-unit rack assembly, the operating ambient temperature of the rack environment
may be greater than room ambient temperature. Therefore, install the equipment in
an environment compatible with the maximum ambient temperature (Tma = +122 °F,
+50 °C) specified by Extron.

2.

Reduced air flow — Install the equipment in a rack so that the amount of air flow
required for safe operation of the equipment is not compromised.

3.

Mechanical loading — When mounting the equipment in the rack, ensure that
uneven mechanical loading does not cause a hazardous condition.

4.

Circuit overloading — When connecting the equipment to the supply circuit, consider
the effect that circuit overloading might have on overcurrent protection and supply
wiring. Consider equipment nameplate ratings when addressing this concern.

5.

Reliable earthing (grounding) — Maintain reliable grounding of rack-mounted
equipment. Pay particular attention to supply connections other than direct connections
to the branch circuit (for example, use of power strips).

Rack mounting the SW2 DVI Plus and SW4 DVI Plus

For optional rack mounting of the models with enclosures of 8.75 inches wide by
3 inches deep (two-input and four-input models), use one of the following procedures:

Mounting on a rack shelf
1.

If feet were previously attached to the bottom of the unit, remove them.

2.

Mount the switcher on the rack shelf, using two 4-40 x 3/16 inch screws in opposite
(diagonal) corners to secure the unit to the shelf (see

figure 34

on the next page).

3.

Install blank panels or other units on the rack shelf as desired.

4.

Install the shelf in the rack.

RRack mounting

Advertising