Analog comparator, Parameter displays for analog comparators – AB Soft PicoTM Controller 1760 User Manual

Page 44

Advertising
background image

Publication 1760-GR001C-EN-P - April 2005

2-18 Drawing a Circuit with Pico

Analog Comparator

Available functions:

• I7 ≥ I8, I7 ≤ I8
• I7 ≥ Setpoint, I7 ≤ Setpoint
• I8 ≥ Setpoint, I8 ≤ Setpoint

The analog comparator can compare voltages from 0V to 10V
(setpoints “0.0” to “10.0”).

Parameter Displays for Analog Comparators

Compare inputs I7 and I8.

TIP

Analog signals of sensors typically fluctuate by
several millivolts. For stable switching the setpoints
should differ by at least 0.2V (switching hysteresis).
Do not use any relay with output energize or
impulse relay coil functions.

ANALOG

I7 8.0 V

A1

I8 4.2 V

+

ANALOG

I7 8.0 V

A1

+

3.2

Input I7

Input I8

Compare Function

Current Value

Analog Compare Number

Parameter Display
(Access Control)

Current Value

Input I7/I8

Compare Function

Setpoint

Current Value

Relay Number

Parameter Display
(Access Control)

Compare input “I7” to a setpoint.

Advertising