Assa 62 User Manual

Page 18

Advertising
background image

Rev. A.3, 5/00

Page- 15

FIG. 13: “SC” SENSTAT WIRING

RED

BLK

GREEN

WHITE

POWER
SUPPLY

+

WHITE AND GREEN WIRES PROVIDE ISOLATED CLOSURE WHEN LOCK IS SECURE.
ORANGE AND WHITE ARE CLOSED WHEN LOCK IS NOT SECURE (AS SHOWN ABOVE).

"SC" LOCK

ORANGE

3.6 DOUBLE DOOR PROCEDURE FOR STATUS REPORTING

Often two Magnalocks are mounted on a double door and are turned on and off together (no
separate control). As to status reporting, it is of course possible to receive a separate Senstat
status signal from each door or you can combine the outputs so that if both locks are secure,
the double door is secure and if either lock is not secure, the double door is not secure.

Simply tie the two white wires together from the two locks. A circuit will be closed between the
two green wires only when both locks are reporting secure. If either is not secure, the circuit
between the two green wires will be open. The orange wires are not used. See Figure 14.

FIG. 14: DOUBLE DOOR WIRING WITH "SC" LOCKS

WHITE

WHITE

"SC" LOCK

"SC" LOCKS ARE INTERWIRED AS SHOWN TO PROVIDE STATUS MONITORING. AN ISOLATED CLOSURE

WILL EXIST BETWEEN THE GREEN WIRES ONLY IF BOTH LOCKS ARE SECURE.

"SC" LOCK

GREEN

GREEN

3.7 DOUBLE DOOR CONTROL SWITCHING

It’s common to control two locks from a single access and/or exit switch on double doors or on
an installation where two locks are mounted on a single door. In nearly all cases, this works
with no problem but occasionally the release can appear to be “sticky” for similar reasons to
those discussed in Section 3.3 This happens when one of the locks is poorly coupled to its
strike plate. This could occur because of an installation problem (the strike plate is not being
allowed to swivel) or because of some obstruction between the plate and magnet surface.
When an electromagnet is not well coupled to its strike plate, its magnetic field collapses so
rapidly that it provides some energy to recirculate in the second magnetic lock, slowing the
release of that lock.

FIG. 14: DOUBLE POLE SWITCHING OF TWO LOCK INSTALLATION

RED

BLK

POWER
SUPPLY

+

MAGNALOCK #1

MAGNALOCK #2

RED

BLK

TWO POLE
SWITCH

Advertising
This manual is related to the following products:

34, 82