2. Control Panel Design Guidelines

The following guidelines are intended to illustrate proper installation of the OIT to

help minimize electrical noise, which may hamper normal operation. It is the

responsibility of the customer to ensure that all wiring and other components

used in the control system meet Class I, Division 2 requirements. This

installation manual is intended only as a general guide to be used in conjunction

with the appropriate Class I, Division 2 installation and wiring requirements.

The customer is ultimately responsible for proper installation.
Pay careful attention to the placement of system components and associated cable

routing. These items can significantly enhance the performance and integrity of

your control application.

2.1. Control Panel Grounding

• The control panel should be connected to a good, high-integrity earth ground

both for safety considerations and shielding purposes. This must be a reliable

earth ground with a low-resistance path. The ideal earth ground would be a

copper grounding rod located close to the OIT and the control panel.

• Hinged doors on control panels do not provide a long term electrical connection

to the rest of the enclosure. Corrosion develops over time and prevents good

electrical contact. For this reason, a separate wire braid should be installed from

the hinged control panel to the rest of the enclosure.

1010-0102, REV 05

INSTALLATION MANUAL

7