It is necessary to follow all installation procedures described in this chapter for

electrical noise immunity and CE compliance.
Your Maple Systems OIT is designed to connect easily to your PLC. External

connectors provide quick connection for power and communications wiring.
• There is one serial port with an RJ-45 shielded jack. This port is used to connect

to the PLC and to configure the OIT.

• A separate three-position terminal block is supplied to provide power to the

OIT.

3.1. Create Custom Slide-In Legend

Please refer to the “Custom Keypad Slide-in Legends” section for details.

3.2. Prepare Panel for OIT Mounting

The OIT3185 and OIT4185 are mounted to a control panel from the front. For a

proper NEMA 4/12 seal, you will need:
• A panel with a maximum thickness of 0.125 inches (3.2 mm).
• A panel with a minimum thickness of 16-gauge (0.059 inches; 1.5 mm) steel or

10-gauge (0.102 inches; 2.6 mm) aluminum. Thinner panels may bow between

the mounting studs, requiring the use of a stiffener on the rear.

• The surface of the panel, where the panel comes into contact with the gasket,

must be free of scratches, pits, and other features that prevent the gasket from

sealing properly.

The diagram in Appendix D shows the dimensions of the panel cutout required for

proper installation. This panel cutout illustration is shown actual size and can be

photocopied to be used as a template. Check photocopy accuracy with the printed

check dimension. The panel cutout should be cleaned and deburred before the OIT

is installed.

3.3. Enclosures

Allow enough spacing within an enclosure for adequate ventilation. For some

applications, you may have to consider heat produced by other devices within a

panel. The ambient temperature around the terminal must be maintained as

specified.

10

OIT3185A/4185A

1010-0104, REV 04

4. OIT Configuration Wiring

The OIT3185 and OIT4185 must be configured for a particular protocol before use.

The OITware-200 or STEPware-100 software (used on a computer with Windows

3.1 or later) is used for OIT configuration. For detailed instructions on installing

and using the software, please refer to the software documentation.

4.1. Connect OIT to PC for Configuration

To configure the OIT using Maple Systems’ configuration software, remove the

PLC/host cable from the serial port on the OIT and connect the OIT to the computer

using an RS-232 serial communications cable (P/N 7431-0096, purchased

separately from Maple Systems). The configuration cable should be connected to

the proper COM port on your computer, then attached to the serial port on the OIT.

See Figure 7 below for serial port pin assignments.

INSTALLATION MANUAL

15

1010-0104, REV 04

CTS

DSR
RTS

DCD
DTR

8

7

6

4

1

RXD

TXD

6

5

RJ-45

OIT

PC

4 Return

Ground 5

TXD 3

RXD 2

9S

1 TXD+
2 TXD-
3 CTS
7 RXD-
8 RXD+

N/C
N/C
N/C
N/C
N/C

9

N/C

Top

8

1

8

1

Pin Configuration

RJ-45 Plug

Printer

Com2

Back

of

OIT

7431-0096

Com1

OIT

PC

OIT Power Supply

Power

Maple Systems

OIT to PC cable

(If mouse is using

Com 1, use Com2)

Figure 7 OIT3185/4185 to PC RS-232 Communication