5

• When mounting the GP unit vertically, ensure that

the left side of the unit faces up (i.e. the power
connector and serial interface should be at the
bottom).

(3) Press the installation fastener hooks securely

into the insertion slots on the GP unit. (Press
the hooks in again to release the lock and
remove the installation fasteners.)

(4) Tighten the installation fasteners with a screw-

driver. There are two insertion slots on both the
top and bottom of the GP unit.

• Tightening the screws with too much force can

damage the GP unit’s plastic case.

• In order to guarantee water repelling effect the

necessary torque is 0.52N

•m [4.60Lb•in].

Wiring

• If the power connector is the following type,

please read "1. Wiring the Power Cord No.1".

• If the power connector is the following type, please

read "2. Wiring the Power Cord No.2".

Mounted

Horizontally

Front and Rear Views

when Mounted

(3)
Press the hooks
securely into
the insertion
slots.

(4)
Tighten the
screw with a
screwdriver

Top

Bottom

Insertion Slots

WARNING

HAZARD OF ELECTRIC SHOCK

Prior to connecting the GP unit's power cord

terminals to the power terminal block, confirm

that the GP unit's power supply is completely

turned OFF, via a breaker, or similar unit.

Supplying a power voltage other than that

specified will damage the power source and

the GP unit.

Since there is no power switch on the GP

unit, be sure to attach a breaker-type switch

to its power cord.

When the FG terminal is connected, be sure

the wire is grounded.

Failure to follow these instructions will result
in death or serious injury.