Input filter, Channel menu, Loop name – Watlow CPC400 User Manual

Page 123: Channel menu 109

Advertising
background image

CPC400 Series User’s Guide

Chapter 5: Menu and Parameter Reference

Doc. 0600-2900-2000

Watlow Anafaze

109

Input Filter

Choose the amount of filtering to apply to the process vari-
able before the value is logged, displayed or used in the con-
trol calculation. The input filter simulates a resistor-
capacitor (RC) filter. Use it to keep the process variable
from varying unrealistically.

When enabled, the process variable responds to a step
change by going to two-thirds of the actual value within the
specified number of scans. One scan is 0.17 seconds for a
CPC404 and 0.33 seconds for a CPC408.

Values: 0 (off) to 255
Default: 3
Modbus Address (Loops 1 to 9): 44409 to 44417
Parameter Number: 84
LogicPro Driver: Database
LogicPro Address (Loops 1 to 9): 84.1 to 84.9

Channel Menu

Use the Channel menu to name and select the feedback for
the loop.

Loop Name

Enter a two-character name for the loop. This name is
shown on the controller display in place of the loop number.

Values: See Table 5.10.
Default: The loop number (01, 02, 03, and so on.)
Modbus Address: 45309 and 45310 for loop 1, 45311 and
45312 for loop 2, and so on
Parameter Number: 132
LogicPro Driver: Database
LogicPro Address: 132.1 and 132.2 for loop 1, 132.3 and
132.4 for loop 2, and so on.

l01 Input r
filter b 3scans

l01 Channel r
Other menus b

l01 Loop name r
b01

Advertising