Setup page – Watlow Power Series Rev H User Manual

Page 37

Advertising
background image

Setup Page

To enter the Setup Page, press the Home and Left keys (

± ¬ ) together while in the Display Loop.

Each of the following menus in the Factory Page are selected by pressing the
Increment/Decrement keys (

У О ). Each press of the button will scroll you up or down

through these main menu options.

To select a parameter within a menu, use the Left/Right arrow keys (

¬ ® ). The parameter

appears in the bottom display.

To select a value for each parameter (either alpha or numeric), use the Increment/Decrement
keys (

У О ). The value appears in the upper display.

Pressing the Home key (

± ) in this menu will return you to the Display Loop.

The Setup Page contains ten menus:

Active if

[algo] is set to [`ftb].

56 r/w

[1SEC] 1

second (0)

[1SEC] 1 second (0)
[4SEC] 4 second (1)

[`FTB] Fixed Time Base

(Sec)

Set the fixed time
base in seconds for
selected zone.

Active: Always.
[cont] is not available if any

input on controller is digital.

[PH2t] phase angle is not

available with 3 phase, 2-leg
controllers.

NOTE: Changing this parameter will
restart the system.

55 r/w

[`Off] non-

operational
(1)

[cont] dc contactor (0)
[`Off] non-operational

(1)

[`Ftb] fixed time base,

zero cross (2)

[Urtb] variable time

base, zero cross (3)

[PH2t] phase angle (4)

[ALgo] Power Control

Algorithm Select

Select power control
algorithm.

[algo]

Setup Control Algorithm

[`Set]

Setup Page

This menu is used to set the control algorithm for the system.

NOTE: Changing the algorithm will restart the system.

*NOTE: These menus are dependent on
the hardware options that are installed
in your controller. Please see the indi-
vidual menus for the options that must
be installed for each of these menus to
appear.

[algo]

[algo] Control

Algorithm

[Ctr1] Control Zone 1
[Opt1] *Options Zone 1
[Ctr2] Control Zone 2
[Opt2] *Options Zone 2
[Ctr3] Control Zone 3
[Opt3] *Options Zone 3
[`ALr] Alarms

Configuration

[COM] *Comms

Configurations

[rEtr] *Retransmit

Configuration

[`Set] Setup Page Select

Go to a setup menu.

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Register

Parameters to Appear

read/write

P a r a m e t e r s , C h a p t e r 6

Wa t l o w P o w e r S e r i e s

6 . 5

NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Control
Methods and Features.