Watlow Power Series Rev H User Manual

Page 41

Advertising
background image

Active if heater diagnostics is

installed.

Active unless Input/Output con-

figuration is 3 phase, 2-leg.

Active if

[algo] is set to [ph2t]

and

[Indf] is set to [`req].

5107 r/w [1]
5207 r/w [2]
5307 r/w [3]

Active load

current

0 to load current rating

[ICur] Inductive Current

Sets the actual mea-
sured current for an
inductive load.

Active if heater diagnostics is

installed.

Active unless Input/Output con-

figuration is 3 phase, 2-leg.

Active if

[algo] is set to [ph2t].

NOTE: Selecting [`act] or [`CLr]
will restart the system.

5106 r/w [1]
5206 r/w [2]
5306 r/w [3]

[Idle] idle

(0)

[`err] invalid request

(-1)

[Idle] idle (0)
[`req] request induc-

tive load factor ad-
justment (1)

[`act] active load fac-

tor adjustment (2)

[`CLr] clears factor (3)

[Indf] Inductive Load

Factor Request

Requests an induc-
tive load factor ad-
justment.

Active if heater diagnostics is

installed.

This set point will only be used if

the requested power is above
20%.

5115 r/w [1]
5215 r/w [2]
5315 r/w [3]

maximum

system cur-
rent

[tol_] to maximum

system current [1
amp increments]
(Heater Low Toler-
ance Set Point to
max Load Current
rating of the Power
Series)

[tol–] High Tolerance

Set Point (A)

Set heater tolerance
high current set point
for the selected zone.
Value is current level
for 100% full on.

Active if heater diagnostics is

installed.

This set point will only be used if

the requested power is above
20%.

5114 r/w [1]
5214 r/w [2]
5314 r/w [3]

0 (0)

[```0] to [tol–] 0

amps to High Toler-
ance Set Point [1
amp increments]
(0 to Heater High
Tolerance Set Point)

[tol_] Low Tolerance Set

Point (A)

Set heater tolerance
low current set point
for the selected zone.
Value is current level
for 100% requested
power and is adjust-
ed actual percentage
of requested power.

Active if heater diagnostics is

installed.

Active unless controller is 3

phase, 2 leg configuration.

Active if

[algo] is set to [Ph2t]

and

[`CLi] is set to [``On].

NOTE: Changing this parameter will
restart the system.

5113 r/w [1]
5213 r/w [2]
5313 r/w [3]

10.0% of load

current

[```0] to [`Cur] 0 to

Load Current Amps
[1 Amp increment;
maximum will be de-
termined by Load
Rating] (0 to Load
Current Amps)

[CL`A] Current Limit Set

Point (A)

Selects the current
limit set point for
current limiting in
chosen zone.

Active if heater diagnostics is

installed.

Active unless controller is 3

phase, 2 leg configuration.

Active if

[algo] is set to [Ph2t].

NOTE: Changing this parameter will
restart the system.

5112 r/w [1]
5212 r/w [2]
5312 r/w [3]

[`OFF] off (0)

[`OFF] off (0)
[``On] on (1)

[`CLi] Current Limit Se-

lect (On/Off)

Selects current limit
method for selected
zone. Used in phase
angle control only.

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Address

Parameters to Appear

read/write

P a r a m e t e r s , C h a p t e r 6

Wa t l o w P o w e r S e r i e s

6 . 9

NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Control
Methods and Features.