Setup prompts and description, Table 9, Setup menu – Watlow Series 922 User Manual

Page 46: Setup

Advertising
background image

46

WATLOW Series 922 User's Manual

How To Program the Series 922, Chapter 6

SETUP Menu

Table 9 -
SETUP Prompts and
Description.

Prompt

Description

Range

Default

Your Settings

ACCESS = (1) PID
To enter PID parameters, use ACCESS (1) & press ENTER.

CH1
PB1H

Enter the Channel 1 Proportional Band value, Heating.

0-900°F/0-500°C/0-500Units 45°F/25°C/25U

RS1H

Enter the Channel 1 Reset value, Heating.

0.00 - 5.00 repeats/minute

0.00

Not displayed if PB1H = 0.

RT1H

Enter the Channel 1 Rate value, Heating.

0.00 - 5.00 minutes

0.00

Not displayed if PB1H = 0.

CT1H

Enter the Channel 1 Cycle Time value, Heating.

1 - 60 seconds

5

Not displayed if PB1H = 0. Dependent on output & OUT1.

RB1H

Enter the Channel 1 Rate Band value, Heating.

0 - 7 times PB1H

0

Not displayed if PB1H = 0.
0 denotes rate is always functional.

DB1

Enter the Current Dead Band value for Channel 1.

-36 to 36°F/-20 to 20°C

0

-20 to 20 Units

PB1C

Enter the Channel 1 Proportional Band value, Cooling.

0-900°F/0-500°C/0-500Units 45°F/25°C/25U

RS1C

Enter the Channel 1 Reset value, Cooling.

0.00 - 5.00 repeats/minute

0.00

Not displayed if PB1C = 0.

RT1C

Enter the Channel 1 Rate value, Cooling.

0.00 - 5.00 minutes

0.00

Not displayed if PB1C = 0.

CT1C

Enter the Channel 1 Cycle Time value, Cooling.

1 - 60 seconds

5

Not displayed if PB1C = 0. Dependent on output &OUT1.

RB1C

Enter the Channel 1 Rate Band value, Cooling.

0 - 7 times PB1C

0

Not displayed if PB1C = 0.
0 denotes rate is always functional.

RETURN Press the ENTER key to return to the SYSTEM prompt.

Press the MODE key to return to the PID prompt.

SETUP

Prompt

Description

Range

Default

Your Settings

ACCESS = (0) CALIB

To enter CALIB parameters use ACCESS (0) and ENTER.

TI XX:XX Read only. Displays the Real Time. HH:MM
HOUR

Enter the hours to display the system time-of-day clock.

0-23 hours

0

MIN

Enter the minutes to display the system time-of-day clock.

0-59 minutes

0

CAL1

Enter the Calibration Offset value for Channel 1.

-90 to 90°F/-50 to 50°C

0

-9.0 to 9.0°F/-5.0 to 5.0°C/U

CAL2

Enter the Calibration Offset value for Channel 2.

-90 to 90°F/-50 to 50°C

0

Dependent on TYP parameter.

-9.0 to 9.0°F/-5.0 to 5.0°C/U

A1H

Enter the Alarm 1 High value. Displayed if AUX1 = AL.
Dependent on AUX1 and ALTYP1 parameters.

See below.

A1L

Enter the Alarm 1 Low value. Displayed if AUX1 = AL.
Dependent on AUX1 and ALTYP1 parameters.

See below.

A2H

Enter the Alarm 2 High value. Displayed if AUX2 = AL.
Dependent on AUX2, ALTYP2, and TYP parameters.

See below.

A2L

Enter the Alarm 2 Low value. Displayed if AUX2 = AL.
Dependent on AUX2, ALTYP2, and TYP parameters.

See below.

RETURN Press the ENTER key to return to the SYSTEM prompt.

Press the MODE key to return to the CALIB prompt.

Make photocopies, keep original clean.

Range

Process Default

Deviation Default

Range

Process Default

Deviation Default

& High Slew Limit

& Low Slew Limit

AXH J

1382°F/750°C

999°F/555°C/U

AXL J

32°F/0°C

-999°F/-555°C/U

K

2282°F/1250°C

999°F/555°C/U

K

-328°F/-200°C/U

-999°F/-555°C/U

T

662°F/350°C

999°F/555°C/U

T

-328°F/-200°C

-999°F/-555°C/U

% RH

100%

555

% RH

0%

-555

RTD Whole

1112°F/600°C

999°F/555°C/U

RTD Whole

-328°F/-200°C

-999°F/-555°C/U

RTD Tenths

392.0°F/200.0°C

999°F/555°C/U

RTD Tenths

-99.9°F/-99.9°C

-999°F/-555°C/U

0 - 5 Whole

1985°F/1985°C

999°F/555°C/U

0 - 5 Whole

-117°F/-117°C

-999°F/-555°C/U

0 - 5 Tenths

198.5°F/198.5°C

999°F/555°C/U

0 - 5 Tenths

-11.7°F/-11.7°C

-999°F/-555°C/U

4 - 20 Whole

1985°F/1985°C

999°F/555°C/U

4 - 20 Whole

-285°F/-285°C

-999°F/-555°C/U

4 - 20 Tenths

198.5°F/198.5°C

999°F/555°C/U

4 - 20 Tenths -28.5°F/-28.5°C

-999°F/-555°C/U

Advertising