Specifications – Watlow Series 922 User Manual

Page 69

Advertising
background image

Appendix

69

WATLOW Series 922 User's Manual

Specifications

Output - Control Per Channel (Single or Dual)

Solid state relay, 0.5A @ 24VAC min. 264 VAC max., opto-isolated, zero
cross switching.

Solid state switch, 20mA @ 20VDC max, open collector switch-to-ground.

4-20mA into 600

load maximum.

Output/Input - Auxiliary

External, plug-in module.

Solid state relays, 2 or 8 ea., 0.5A @ 24VAC min. 264 VAC max.

Auxiliary supply: 21 to 33VDC, 25mA maximum.

Switched DC signal provides a minimum turn on voltage of 3VDC in a
minimum 500

load. Maximum on voltage not greater than 32VDC into an

infinite load.

Output - Analog Retransmit

Device driven must have an input impedance > 10k

.

Reference: 0 Units = 0 Volts.

Scalable: 1mV, 2mV, 5mV, or 10mV per LSD.

Maximum voltage Span: -9.5 to +9.5 volts.

Accuracy

Calibration Accuracy and Sensor Conformity:

±

0.15% of span,

±

1 digit at

77

°

F

±

5

°

F (25

°

C

±

3

°

C) ambient & rated line voltage

±

10%.

Accuracy Span: 1000

°

F or 540

°

C minimum.

Temperature Stability: 0.18

°

F/

°

F (0.1

°

C/

°

C) change in ambient.

Voltage Stability:

±

0.01% of span / % of rated line voltage.

Communications

Serial data communications.

RS-422A or RS-423A (RS-232C compatible).

Most operator indication and controls.

ANSI X3.28 protocol, or XON/XOFF protocol.

Isolated.

DB-9 Female connector.

Terminals

#6 compression type screw terminals.

Power

115/230VAC

±

10%, 50/60Hz

±

5%.

18VA maximum.

Data retention upon power failure via nonvolatile memory.

Operating Environment

32 to 130

°

F/0 to 55

°

C.

0 to 90% RH, non-condensing.

Dimensions

Height:

3.8 in.

(96.52 mm)

Width:

3.8 in.

(96.52 mm)

Overall depth:

7.0 in.

(177.80 mm)

Behind panel depth:

6.0 in.

(152.50 mm)

with connector for
communication and events:

8.8 in.

(223.52 mm)

Weight:

2.8 lb

(1.27 kg)