Programming program menu program menu – Watlow Series 922 Retrofit User Manual

Page 68

Advertising
background image

WATLOW Series 922 User's Manual

60

How To Program the Series 922, Chapter 6

Programming

PROGRAM Menu

PROGRAM Menu

SETPOINT step is executed. These events only appear when the 8
output event board is connected to the Series 922.
Range: OFF or ON

Default: Unprogrammed

OFF = Event OFF

ON = Event ON

From RETURN, you can go back to the SYSTEM prompt by pressing
the ENTER key, or return to FILE? by pressing the MODE key.

One of six step types under the PROGRAM menu of the Series 922
that can be programmed as a step or file. You can jump from one
step to another within a file.

The Series 922 will jump loop to any step within your current file. You
cannot jump loop to another step in another file.
Range: 1 to 99

Default: 1

The number of times that the Series 922 jumps to the step that was
specified by the JS step. 0 = Infinite number of jumps.
Range: 0 to 100

Default: 0

From RETURN, you can go back to the SYSTEM prompt by pressing
the ENTER key, or return to FILE? by pressing the MODE key.

One of six step types under the PROGRAM menu of the Series 922
that can be programmed to wait for a specific amount of time, a
desired set point or both. When either or both are used, they must be
true before the program continues.

Value the system compares against the process variable of Channel
1, and waits for, before proceeding to the next step of the program.
Range: R1L to R1H

Default: Unprogrammed

Value the system compares against the process variable of Channel
2, and waits for, before proceeding to the next step of the program.
This parameter will not appear if "T" or "P" (Channel 1 only) in the
TYP parameter under the SPCLFUNC menu have been selected.
Range: R2L to R2H

Default: Unprogrammed

The hours the system will wait for, relative to when the step began.
This is not a measure of time-of-day.
Range: 0 to 23 hours

Default: Unprogrammed

Represents the minutes the system will wait for, relative to when the
step began. This is not a measure of time-of-day.
Range: 0 to 59 minutes

Default: Unprogrammed

W2 ( )

EV3 ( )

EV4 ( )

EV5 ( )

EV6 ( )

EV7 ( )

EV8 ( )

RETURN

JUMPLOOP

JS ( )

JC ( )

RETURN

WAITFOR

W1 ( )

WHR ( )

WMN ( )